Artikel Nr.: LY1-C40M/2(S)

Key Specifications:

Modell
LY1-C40M/2(S)

Typ
Class I+II / Type 1+2 AC SPD

Pole
2P / L+N Compact Design

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

Iimp
7kA, 10/350μs

In / Imax
20kA / 40kA, 8/20μs

Back-Up Fuse
63A gL / gG Max.

Montage
35mm DIN Rail

Jetzt zitieren

    Compact Type 1+2 AC Surge Protection for Space-Limited Panels

    LY1-C40M/2(S) is a compact two-pole pluggable Type 1+2 AC surge protective device for single-phase L+N distribution systems. Its mini modular construction combines a 7kA impulse-current capability with 20kA nominal and 40kA maximum discharge ratings, helping protect power circuits while reducing the DIN-rail space required inside compact panels.


    Compact 2P / L+N design for single-phase distribution systems

    7kA Iimp, 20kA In, and 40kA Imax surge ratings

    75V to 440V AC versions for different low-voltage systems

    Pluggable modules with visual status indication and optional remote contact

    Suitable Applications

    LY1-C40M/2(S) is suitable for single-phase L+N power systems requiring compact Type 1+2 surge protection in space-limited distribution and equipment panels.

    Compact Distribution Boxes

    For space-limited single-phase distribution boxes requiring L+N surge protection.

    Control Cabinets

    Suitable for automation cabinets, machinery panels, and compact industrial control systems.

    🔋

    UPS Power Systems

    Helps protect UPS input or output circuits when voltage and protection configuration match the installation.

    Solar Inverter AC Output

    For the AC output side of solar inverters when the selected voltage version matches the system.

    FAQ

    Common questions about LY1-C40M/2(S) compact two-pole pluggable Type 1+2 AC surge protective device selection.

    What is LY1-C40M/2(S) used for?

    LY1-C40M/2(S) is used for surge protection in compact single-phase L+N distribution systems, including small distribution boxes, equipment cabinets, UPS systems, and solar inverter AC output circuits.

    Is LY1-C40M/2(S) a single-pole or two-pole SPD?

    The LY1-C40M/2(S) model is a two-pole device intended for L+N single-phase circuits. The existing page title should therefore be changed from single-pole to two-pole.

    What surge ratings does this SPD provide?

    The device provides 7kA impulse discharge current Iimp, 20kA nominal discharge current In, and 40kA maximum discharge current Imax.

    What voltage options are available?

    Maximum continuous operating voltage options include 75V, 150V, 275V, 320V, 385V, and 440V AC. The voltage version must be selected according to the nominal system voltage.

    What is the benefit of the compact pluggable design?

    The compact format reduces DIN-rail space, while the pluggable modules make inspection and replacement easier without replacing the complete wired base.

    What should be confirmed before ordering?

    Confirm the system voltage, L+N circuit arrangement, required surge ratings, 63A maximum backup-fuse coordination, DIN-rail space, conductor size, and remote-contact requirement.

    Technische Daten

    Electrical, mechanical, and installation data for LY1-C40M/2(S) compact two-pole pluggable Type 1+2 AC surge protective device selection.

    Parameter75V150V275V320V385V440V
    IEC Elektrisch
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc75V150V275V320V385V440V
    Nominal Discharge Current In, 8/20μs20kA
    Maximum Discharge Current Imax, 8/20μs40kA
    Impulse Discharge Current Iimp, 10/350μs7kA
    Voltage Protection Level Up0.4kV1.0kV1.5kV1.6kV1.8kV2.0kV
    Response Time tA<25ns
    Back-Up Fuse Max.63A gL / gG
    Short-Circuit Current Rating ISCCR25kA
    TOV Withstand 5s UT90V180V335V335V335V580V
    TOV 120min UT115V230V440V440V440V765V
    TOV ModeWiderstandsfähigWiderstandsfähigSicheres VersagenSicheres VersagenSicheres VersagenSicheres Versagen
    Mechanik und Umwelt
    Betriebstemperaturbereich-40°C to +70°C
    Zulässige Betriebsfeuchtigkeit5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Klemmenschrauben-Drehmoment39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Montage35mm DIN Rail, EN 60715
    Grad des SchutzesIP20, built-in
    Material des GehäusesThermoplastic, UL94 V-0
    Thermischer SchutzJa
    Betriebszustand/StörungsanzeigeGreen: OK / Red: Defect
    Remote ContactsOptional
    RC-SchaltleistungAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the required AC voltage rating, two-pole L+N circuit arrangement, 63A maximum backup fuse, conductor size, available DIN-rail space, and optional remote contact before ordering.

    ■ Interne Konfiguration


    ■ Abmessungen und Verpackung


    ■ Anschlussschema

    Jetzt mit der Anpassung beginnen

    Wir bieten ein umfassendes Angebot an maßgeschneiderten Dienstleistungen und arbeiten bei jedem Schritt eng mit unseren Kunden zusammen, vom Konzept bis zur Auslieferung.

    Andere&Produkte

    Unser Team orientiert sich stets an den Bedürfnissen unserer Kunden und bietet professionelle Beratung und Unterstützung, um Ihre Zufriedenheit zu gewährleisten.

    ALLES, WAS SIE NICHT FINDEN KONNTEN?

    Sprechen Sie mit unserem Vertrieb

    Da wir wissen, dass jedes Unternehmen einzigartig ist, bieten wir maßgeschneiderte Dienstleistungen an, um sicherzustellen, dass unsere Produkte perfekt auf Ihre spezifischen Bedürfnisse zugeschnitten sind:

    • Umfassende Broschüre zum Herunterladen
    • 15 Jahre Erfahrung in der Fabrik
    • Schnelle Lieferung
    • OEM&ODM
    • Niedriger Preis
    • Kleiner MQQ

    SENDEN SIE UNS EINE E-MAIL

    devin@cnspd.com

    Kontakt

    Wir bewerten und verbessern unsere Prozesse ständig, um sicherzustellen, dass wir die effizientesten und zuverlässigsten Elektroprodukte auf dem Markt liefern.