Nº do artigo: LY1-C40PV/2(S)

Key Specifications:

Modelo
LY1-C40PV/2(S) 1000V

Tipo de DPS
Class I+II / Type 1+2 DC SPD

Maximum DC Voltage
1000V DC

Pole Configuration
2-Pole Pluggable Design

Modo de proteção
DC+–PE / DC−–PE

In / Imax
20kA / 40kA, 8/20μs

Impulse Current Iimp
6.25kA, 10/350μs

Padrão
IEC 61643-31:2018

Citar agora

    Type 1+2 Surge Protection for 1000V DC Solar PV Systems

    LY1-C40PV/2(S) 1000V is a two-pole pluggable Type 1+2 DC surge protective device designed for photovoltaic strings, combiner boxes, inverter DC inputs, and high-voltage DC distribution systems. Its high-energy MOV modules provide protection for both positive and negative DC conductors, with 20kA nominal discharge current, 40kA maximum discharge current, and a listed 6.25kA impulse current.


    Class I+II / Type 1+2 protection for 1000V DC systems

    Two-pole protection for DC+ and DC− conductors

    20kA In, 40kA Imax, and 6.25kA Iimp capability

    Replaceable cartridges with visual status indication

    Suitable Applications

    LY1-C40PV/2(S) 1000V is designed for high-voltage photovoltaic and DC power systems requiring coordinated protection of both positive and negative conductors.

    PV String Combiner Boxes

    Protects 1000V DC photovoltaic strings and combiner-box circuits against lightning and switching surges.

    PV Inverter DC Inputs

    Suitable for protecting the DC input side of string, hybrid, and central solar inverters.

    DC Distribution Cabinets

    For 1000V DC distribution cabinets, switching panels, and high-voltage DC equipment circuits.

    🔋

    Energy Storage DC Systems

    Suitable for compatible battery charging cabinets and energy-storage DC circuits up to 1000V DC.

    FAQ

    Common questions about LY1-C40PV/2(S) 1000V two-pole pluggable Type 1+2 DC surge protective device selection and installation.

    What is LY1-C40PV/2(S) 1000V used for?

    It is designed to protect 1000V DC photovoltaic and DC power systems against lightning-induced surges and switching transient overvoltage. Typical locations include PV combiner boxes, inverter DC inputs, and DC distribution cabinets.

    Is this a Type 1+2 DC SPD?

    Yes. The product is classified as Class I+II / Type 1+2 and lists both an 8/20μs discharge-current rating and a 10/350μs impulse-current rating.

    What discharge current ratings does it provide?

    It provides 20kA nominal discharge current In, 40kA maximum discharge current Imax, and a listed 6.25kA impulse discharge current Iimp.

    What does the two-pole configuration protect?

    The two-pole configuration provides separate surge-protection paths for the positive and negative DC conductors relative to protective earth.

    Can the protection cartridges be replaced?

    Yes. The pluggable design allows individual protection cartridges to be inspected or replaced without removing the permanently wired base.

    What should be confirmed before ordering?

    Confirm the maximum PV system voltage, 1000V DC operating requirement, DC+ and DC− protection arrangement, required Up level, backup-fuse coordination, conductor size, DIN-rail space, and remote-contact requirement.

    Dados técnicos

    Electrical, mechanical, environmental, and installation data for LY1-C40PV/2(S) 1000V two-pole pluggable Type 1+2 DC surge protective device selection.

    ParâmetroLY1-C40PV/2(S) 1000V
    DC Electrical
    SPD ClassificationClass I+II / Type 1+2
    Nominal DC System Voltage Uo / Un1000V DC
    Maximum Continuous Operating Voltage Ucpv1000V DC
    Modo de proteçãoDC+–PE / DC−–PE
    Nominal Discharge Current In, 8/20μs20kA
    Maximum Discharge Current Imax, 8/20μs40kA
    Impulse Discharge Current Iimp, 10/350μs6,25kA
    Voltage Protection Level Up3,6kV
    Response Time tA<25ns
    Back-Up Fuse Max.125A gL / gG
    Short-Circuit Current Rating ISCPV25kA / 50kA
    Protective ElementHigh-Energy MOV
    ConformidadeIEC 61643-31:2018
    Mecânica e ambiente
    Gama de temperaturas de funcionamento-40°C to +70°C
    Humidade de funcionamento admissível5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Torque do parafuso do terminal4.5Nm
    Conductor Cross Section Max.35mm² solid/stranded; 25mm² flexible
    Montagem35mm DIN Rail, EN 60715
    Grau de proteçãoIP20, built-in
    Material da caixaThermoplastic, UL94 V-0
    Proteção térmicaSim
    Estado de funcionamento / Indicação de avariaGreen: OK / Red: Defect
    Remote ContactOpcional
    Remote Contact Switching CapacityAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    Remote Contact Conductor Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm that the maximum open-circuit voltage of the PV array does not exceed the selected SPD rating. Also verify the grounding system, required voltage protection level, backup-fuse coordination, conductor size, cable length, and installation location before ordering.

    Configuração interna


    ■ Dimensões e embalagem


    Diagrama de ligação

    Comece a personalizar agora

    Oferecemos uma gama completa de serviços personalizados, trabalhando em estreita colaboração com os nossos clientes em todas as fases do processo, desde a conceção até à entrega final.

    Outros&Produtos

    A nossa equipa é sempre guiada pelas necessidades dos nossos clientes, fornecendo aconselhamento profissional e apoio para garantir a sua satisfação.

    QUALQUER COISA QUE NÃO CONSEGUISTE ENCONTRAR?

    Fale com os nossos comerciais

    Sabemos que cada empresa é única, por isso oferecemos serviços personalizados para garantir que os nossos produtos correspondem perfeitamente às suas necessidades específicas:

    • Brochura completa que pode ser descarregada
    • 15 anos de experiência na fábrica
    • Entrega rápida
    • OEM&ODM
    • Preço baixo
    • Pequena MQQ

    ENVIAR-NOS UMA MENSAGEM DE CORREIO ELECTRÓNICO

    devin@cnspd.com

    Contactar-nos

    Avaliamos e melhoramos constantemente os nossos processos para garantir que estamos a fornecer os produtos eléctricos mais eficientes e fiáveis do mercado.