Item No.: LY1-C40/3(S)

Key Specifications:

Model
LY1-C40/3(S)

Type
Class II / Type 2 AC SPD

Pole Configuration
3-Pole Pluggable Design

Protection Mode
L-PE / N-PE

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
20kA / 40kA, 8/20μs

Protection Element
High-Energy MOV

Mounting
35mm DIN Rail

Quote Now

    Reliable Type 2 AC Surge Protection for Three-Phase Circuits

    LY1-C40/3(S) is a three-pole pluggable Type 2 AC surge protective device designed for three-phase low-voltage distribution systems. Its high-energy MOV modules provide fast transient-voltage limitation with 20kA nominal discharge current and 40kA maximum discharge current, while the replaceable cartridge design simplifies inspection and maintenance.


    Class II / Type 2 protection for three-phase AC systems

    Three-pole design for coordinated multi-phase protection

    20kA nominal and 40kA maximum discharge current

    Pluggable cartridges with visual indication and optional remote contact

    Suitable Applications

    LY1-C40/3(S) is suitable for three-phase AC systems requiring modular Type 2 surge protection in distribution boards, industrial control panels, commercial buildings, and solar AC power systems.

    Three-Phase Distribution Boards

    For Type 2 surge protection in commercial and industrial three-phase distribution panels.

    Industrial Control Panels

    Suitable for machinery controls, factory automation, HVAC systems, and electrical equipment cabinets.

    🏢

    Commercial Buildings

    Helps protect office buildings, retail facilities, and commercial electrical systems from transient overvoltage.

    Solar Inverter AC Panels

    For three-phase solar inverter AC-side panels when the selected Uc version matches the system voltage.

    FAQ

    Common questions about LY1-C40/3(S) three-pole pluggable Type 2 AC surge protective device selection and installation.

    What is LY1-C40/3(S) used for?

    LY1-C40/3(S) is used to limit transient overvoltage in three-phase low-voltage AC systems. It is suitable for distribution boards, industrial control cabinets, machinery power panels, and commercial electrical systems.

    Is LY1-C40/3(S) a Type 2 SPD?

    Yes. LY1-C40/3(S) is classified as a Class II / Type 2 AC surge protective device. The incorrect Type 1CA wording should not be used.

    What discharge current ratings does it provide?

    The SPD provides 20kA nominal discharge current In and 40kA maximum discharge current Imax. The technical table also lists a 7kA impulse-current parameter.

    What voltage options are available?

    Maximum continuous operating voltage options include 75V, 150V, 275V, 320V, 385V, and 440V AC. Select the correct version according to the nominal system voltage.

    What is the benefit of the pluggable design?

    Each cartridge can be inspected or replaced independently without removing the permanently wired base, reducing maintenance time and simplifying servicing.

    What should be confirmed before ordering?

    Confirm the nominal system voltage, required Uc and Up level, three-pole protection arrangement, 125A maximum backup-fuse coordination, conductor size, DIN-rail space, and remote-contact requirement.

    Technical Data

    Electrical, mechanical, environmental, and installation data for LY1-C40/3(S) three-pole pluggable Type 2 AC surge protective device selection.

    Parameter 75V 150V 275V 320V 385V 440V
    IEC Electrical
    Nominal AC Voltage Uo / Un 60V 120V 230V 230V 230V 400V
    Maximum Continuous Operating Voltage Uc 75V 150V 275V 320V 385V 440V
    Nominal Discharge Current In, 8/20μs 20kA
    Maximum Discharge Current Imax, 8/20μs 40kA
    Listed Impulse Current Iimp, 10/350μs 7kA
    Voltage Protection Level Up 0.4kV 1.0kV 1.5kV 1.6kV 1.8kV 2.0kV
    Response Time tA <25ns
    Back-Up Fuse Max. 125A gL / gG
    Short-Circuit Current Rating ISCCR 25kA / 50kA
    TOV Withstand 5s UT 90V 180V 335V 335V 335V 580V
    TOV 120min UT 115V 230V 440V 440V 440V 765V
    TOV Mode Withstand Withstand Safe Fail Safe Fail Safe Fail Safe Fail
    Mechanical & Environmental
    Operating Temperature Range -40°F to +158°F [-40°C to +70°C]
    Permissible Operating Humidity 5%–95%
    Atmospheric Pressure / Altitude 80kPa–106kPa / -500m to 2000m
    Terminal Screw Torque 39.9 lbf·in [4.5Nm]
    Conductor Cross Section Max. 2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Mounting 35mm DIN Rail, EN 60715
    Degree of Protection IP20, built-in
    Housing Material Thermoplastic, UL94 V-0
    Thermal Protection Yes
    Operating State / Fault Indication Green: OK / Red: Defect
    Remote Contacts Optional
    RC Switching Capacity AC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max. 16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the nominal system voltage, required Uc and Up level, three-pole protection arrangement, 125A maximum backup fuse, conductor size, DIN-rail space, and optional remote contact before ordering.

    ■ Internal Configuration


    ■ Dimensions & Packaging


    ■ Connection Diagram

    Start Customizing Now

    We offer a full range of customised services, working closely with our customers every step of the way, from concept design to final delivery.

    Other&Products

    Our team is always guided by the needs of our customers, providing professional consultation and support to ensure your satisfaction.

    ANYTHING YOU COULDN’T FIND?

    Talk With Our Sales

    We know that every business is unique, so we offer customized services to ensure that our products perfectly match your specific needs:

    • Comprehensive brochure you can download
    • 15 years factory experience
    • Fast delivery
    • OEM&ODM
    • Low price
    • Small MQQ

    SEND US AN EMAIL

    devin@cnspd.com

    Contact Us

    We constantly evaluate and improve our processes to ensure that we are delivering the most efficient and reliable electrical products on the market.