Item No.: LY1-D20/3(S)+1

Key Specifications:

Model
LY1-D20/3(S)+1

Type
Class II+III / Type 2+3 AC SPD

System
3P+N Three-Phase System

Protection Mode
L-N / N-PE

Protection Elements
High-Energy MOV + GDT

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
10kA / 20kA, L-N and N-PE

Mounting
35mm DIN Rail

Quote Now

    Compact Type 2+3 AC Surge Protection for 3P+N Systems

    LY1-D20/3(S)+1 is a compact 3P+N pluggable Type 2+3 AC surge protective device for three-phase plus neutral systems. Its coordinated MOV and GDT structure provides L-N and N-PE protection with 10kA nominal discharge current and 20kA maximum discharge current for downstream and final-distribution applications.


    Class II+III / Type 2+3 protection for downstream AC circuits

    3P+N configuration with L-N and N-PE protection

    Coordinated MOV and GDT surge-protection technology

    Pluggable modules with visual indication and optional remote contact

    Suitable Applications

    LY1-D20/3(S)+1 is suitable for three-phase plus neutral systems requiring coordinated Type 2+3 surge protection close to downstream equipment and final distribution circuits.

    Sub-Distribution Boards

    For downstream protection in commercial and industrial three-phase plus neutral distribution boards.

    Industrial Control Panels

    Suitable for machinery controls, automation cabinets, HVAC panels, and production equipment.

    🏢

    Commercial Facilities

    Helps protect office buildings, retail systems, building controls, and sensitive commercial loads.

    Solar Inverter AC Panels

    For three-phase solar inverter AC-side panels when the selected Uc rating matches the system voltage.

    FAQ

    Common questions about LY1-D20/3(S)+1 compact 3P+N pluggable Type 2+3 AC surge protective device selection.

    What is LY1-D20/3(S)+1 used for?

    LY1-D20/3(S)+1 is used for downstream and final-distribution surge protection in three-phase plus neutral AC systems. It helps limit transient overvoltage through coordinated L-N and N-PE protection paths.

    What does 3P+N mean?

    3P+N means the SPD is designed for three phase conductors plus neutral, with MOV protection on the L-N paths and a GDT protection path between N-PE.

    Is LY1-D20/3(S)+1 a Type 2 or Type 3 SPD?

    LY1-D20/3(S)+1 is classified as Class II+III / Type 2+3, making it suitable for coordinated downstream and final-distribution surge protection.

    What protection technology does it use?

    It combines high-energy MOV protection on the L-N paths with a GDT on the N-PE path, providing coordinated surge protection for three-phase plus neutral systems.

    What discharge current ratings does it provide?

    It provides 10kA nominal discharge current and 20kA maximum discharge current on both the L-N and N-PE protection paths.

    What should be confirmed before ordering?

    Confirm the nominal L-N voltage, required Uc and Up level, 3P+N wiring arrangement, 125A maximum backup-fuse coordination, conductor size, DIN-rail space, and optional remote-contact requirement.

    Technical Data

    Electrical, mechanical, environmental, and installation data for LY1-D20/3(S)+1 compact 3P+N pluggable Type 2+3 AC surge protective device selection.

    Parameter75V150V275V320V385V440V
    IEC Electrical
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc, L-N75V150V275V320V385V440V
    Maximum Continuous Operating Voltage Uc, N-PE255V
    Nominal Discharge Current In, L-N / N-PE10kA / 10kA, 8/20μs
    Maximum Discharge Current Imax, L-N / N-PE20kA / 20kA, 8/20μs
    Voltage Protection Level Up, L-N / N-PE0.2kV / 1.5kV0.6kV / 1.5kV1.3kV / 1.5kV1.5kV / 1.5kV1.5kV / 1.5kV1.8kV / 1.5kV
    Follow Current Interrupt Rating Ifi, N-PE100 ARMS
    Response Time tA, L-N / N-PE<25ns / <100ns
    Back-Up Fuse Max.125A gL / gG
    Short-Circuit Current Rating ISCCR, L-N10kA
    TOV Withstand 5s UT, L-N90V180V335V335V335V580V
    TOV 120min UT, L-N115V230V440V440V440V765V
    TOV ModeWithstandWithstandSafe FailSafe FailSafe FailSafe Fail
    TOV Withstand 200ms UT, N-PE1200V
    Mechanical & Environmental
    Operating Temperature Range-40°C to +70°C
    Permissible Operating Humidity5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Terminal Screw Torque39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Mounting35mm DIN Rail, EN 60715
    Degree of ProtectionIP20, built-in
    Housing MaterialThermoplastic, UL94 V-0
    Thermal ProtectionYes
    Operating State / Fault IndicationGreen: OK / Red: Defect
    Remote ContactsOptional
    RC Switching CapacityAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the nominal L-N voltage, required Uc and Up level, 3P+N wiring arrangement, 125A maximum backup fuse, conductor size, DIN-rail space, and optional remote contact before ordering.

    ■ Internal Configuration


    ■ Dimensions & Packaging


    ■ Connection Diagram

    Start Customizing Now

    We offer a full range of customised services, working closely with our customers every step of the way, from concept design to final delivery.

    Other&Products

    Our team is always guided by the needs of our customers, providing professional consultation and support to ensure your satisfaction.

    ANYTHING YOU COULDN’T FIND?

    Talk With Our Sales

    We know that every business is unique, so we offer customized services to ensure that our products perfectly match your specific needs:

    • Comprehensive brochure you can download
    • 15 years factory experience
    • Fast delivery
    • OEM&ODM
    • Low price
    • Small MQQ

    SEND US AN EMAIL

    devin@cnspd.com

    Contact Us

    We constantly evaluate and improve our processes to ensure that we are delivering the most efficient and reliable electrical products on the market.