Artikel Nr.: LY1-D20/4(S)

Key Specifications:

Modell
LY1-D20/4(S)

Typ
Class II+III / Type 2+3 AC SPD

Pole Configuration
4P / 3P+N Pluggable Design

Schutzmodus
L-PE / N-PE

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
10kA / 20kA, 8/20μs

Protection Element
High-Energy MOV

Montage
35mm DIN Rail

Jetzt zitieren

    Compact Type 2+3 AC Surge Protection for 3P+N Systems

    LY1-D20/4(S) is a four-pole pluggable Type 2+3 AC surge protective device designed for three-phase plus neutral distribution systems. Its high-energy MOV modules provide coordinated surge suppression across phase and neutral paths, with 10kA nominal discharge current and 20kA maximum discharge current for downstream and final-distribution protection.


    Class II+III / Type 2+3 protection for downstream AC systems

    4P / 3P+N design for three-phase four-wire circuits

    10kA nominal and 20kA maximum discharge current

    Replaceable cartridges with visual indication and optional remote contact

    Suitable Applications

    LY1-D20/4(S) is suitable for three-phase plus neutral downstream and final-distribution AC systems requiring coordinated four-pole Type 2+3 surge protection.

    Unterverteilerschränke

    For downstream protection in commercial and industrial three-phase plus neutral distribution panels.

    Industrial Control Panels

    Suitable for machinery controls, production equipment, HVAC systems, and factory automation cabinets.

    🏢

    Commercial Facilities

    Helps protect offices, shopping facilities, building automation systems, and commercial electrical loads.

    Solar Inverter AC Panels

    For three-phase solar inverter AC-side panels when the selected Uc version matches the system voltage.

    FAQ

    Common questions about LY1-D20/4(S) four-pole pluggable Type 2+3 AC surge protective device selection and installation.

    What is LY1-D20/4(S) used for?

    LY1-D20/4(S) is used for downstream surge protection in three-phase plus neutral AC distribution systems. It is suitable for sub-distribution boards, control cabinets, commercial power systems, and final equipment circuits.

    What does 4P or 3P+N mean?

    4P or 3P+N means the SPD provides protection for three phase conductors and the neutral conductor in a three-phase four-wire electrical system.

    Is LY1-D20/4(S) a Type 2 or Type 3 SPD?

    LY1-D20/4(S) is classified as Class II+III / Type 2+3, making it suitable for coordinated downstream and final-distribution surge protection.

    What discharge current ratings does it provide?

    It provides 10kA nominal discharge current In and 20kA maximum discharge current Imax, both based on the 8/20μs current waveform.

    What voltage options are available?

    Available maximum continuous operating voltage options are 75V, 150V, 275V, 320V, 385V, and 440V AC. Select the correct version according to the nominal system voltage.

    What should be confirmed before ordering?

    Confirm the nominal system voltage, required Uc and Up level, 3P+N protection arrangement, 125A maximum backup-fuse coordination, conductor size, DIN-rail space, and remote-contact requirement.

    Technische Daten

    Electrical, mechanical, environmental, and installation data for LY1-D20/4(S) four-pole pluggable Type 2+3 AC surge protective device selection.

    Parameter75V150V275V320V385V440V
    IEC Elektrisch
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc75V150V275V320V385V440V
    Nominal Discharge Current In, 8/20μs10kA
    Maximum Discharge Current Imax, 8/20μs20kA
    Voltage Protection Level Up0.2kV0.6kV1.3kV1.5kV1.5kV1.8kV
    Response Time tA<25ns
    Back-Up Fuse Max.125A gL / gG
    Short-Circuit Current Rating ISCCR10kA
    TOV Withstand 5s UT90V180V335V335V335V580V
    TOV 120min UT115V230V440V440V440V765V
    TOV ModeWiderstandsfähigWiderstandsfähigSicheres VersagenSicheres VersagenSicheres VersagenSicheres Versagen
    Mechanik und Umwelt
    Betriebstemperaturbereich-40°F to +158°F [-40°C to +70°C]
    Zulässige Betriebsfeuchtigkeit5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Klemmenschrauben-Drehmoment39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Montage35mm DIN Rail, EN 60715
    Grad des SchutzesIP20, built-in
    Material des GehäusesThermoplastic, UL94 V-0
    Thermischer SchutzJa
    Betriebszustand/StörungsanzeigeGreen: OK / Red: Defect
    Remote ContactsOptional
    RC-SchaltleistungAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the nominal system voltage, required Uc and Up level, 3P+N protection arrangement, 125A maximum backup fuse, conductor size, DIN-rail space, and optional remote contact before ordering.

    ■ Interne Konfiguration


    ■ Abmessungen und Verpackung


    ■ Anschlussschema

    Jetzt mit der Anpassung beginnen

    Wir bieten ein umfassendes Angebot an maßgeschneiderten Dienstleistungen und arbeiten bei jedem Schritt eng mit unseren Kunden zusammen, vom Konzept bis zur Auslieferung.

    Andere&Produkte

    Unser Team orientiert sich stets an den Bedürfnissen unserer Kunden und bietet professionelle Beratung und Unterstützung, um Ihre Zufriedenheit zu gewährleisten.

    ALLES, WAS SIE NICHT FINDEN KONNTEN?

    Sprechen Sie mit unserem Vertrieb

    Da wir wissen, dass jedes Unternehmen einzigartig ist, bieten wir maßgeschneiderte Dienstleistungen an, um sicherzustellen, dass unsere Produkte perfekt auf Ihre spezifischen Bedürfnisse zugeschnitten sind:

    • Umfassende Broschüre zum Herunterladen
    • 15 Jahre Erfahrung in der Fabrik
    • Schnelle Lieferung
    • OEM&ODM
    • Niedriger Preis
    • Kleiner MQQ

    SENDEN SIE UNS EINE E-MAIL

    devin@cnspd.com

    Kontakt

    Wir bewerten und verbessern unsere Prozesse ständig, um sicherzustellen, dass wir die effizientesten und zuverlässigsten Elektroprodukte auf dem Markt liefern.