Data Teknis
| Tipe | |
| SPD sesuai dengan EN 61643-31 / IEC 61643-31 |
tipe 1+2 / kelas I+II |
| Tegangan operasi DC maksimal yang terus-menerus (DC+)-PE, (DC-)-PE, (DC+)-(DC-) Ucpv |
1500 V DC |
| Arus pelepasan nominal (8/20μs) In |
20 kA |
| Arus pelepasan maksimum (8/20μs) Imax |
40 kA |
| Arus impuls maksimum (8/20μs) Itotal |
40 kA |
| Arus impuls maksimum (10/350μs) Iimp |
6.25 kA |
| Arus impuls maksimum (10/350μs) Itotal |
12.5 kA |
| arus kontinu untuk aplikasi PV ICPV |
0,2 mA |
| tingkat perlindungan tegangan (DC+)-PE, (DC-)-PE (DC+)-(DC-) Up |
5,0 kV |
| waktu respons tA |
25 ns (L-N) |
| penilaian arus hubung singkat Iscpv |
2000 A |
| arus sisa a.c. dan d.c. IPE |
0,3 mA(DC), 0,3 mA(AC), |
| rentang kelembaban |
5% … 95% |
| rentang suhu operasi TU |
-40°C … +70°C |
| tekanan atmosfer dan ketinggian |
80k Pa … 106k Pa, -500 m … 2000 m |
| indikasi status operasi / kesalahan |
Hijau ok / Merah cacat |
| Jumlah port |
Satu port |
| Luas penampang (maks.) |
2 AWG (Padat, Tersendat) / 4 AWG (Fleksibel) 35 mm2 (Padat, Tersendat) / 25 mm2 (Fleksibel) |
| Untuk dipasang pada |
Rel DIN 35 mm sesuai dengan EN 60715 |
| Enclosure material |
thermoplastic |
| Place of installation |
indoor installation |
| Derajat perlindungan |
IP 20 |
| Capacity |
4 module(s), DIN 43880 |
| Approvals |
– |
| Type of remote signalling contact |
changeover contact |
| a.c. switching capacity |
250V / 0.5 A |
| d.c. switching capacity |
250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals |
max. 1.5 mm2 solid / flexible |
| Remote signalling alarming mode |
Normal: closed; failure: open-circuit |
| Acessibility |
Inaccessible |
| Protection fuction |
Overcurrent |
| PV earthing system |
Earthed and Unearthed (both) |
| SPD failure mode (OCFM/SCFM) |
OCFM |
Circuit Diagram

Installation, Usage And Maintenance
The installation of SPD should be based on Fig. 3 IEC 60364-5-53. The cross-sectional area of ground wire should not be less than 4 mm2, and the length of total lead not more than 0.5m.
The minimum distance from any earthed conductive surface at which the SPD can be installed is 8mm.
Connection of remote signalling alarm: the SPD is provided with remote signalling interfaces (NC, COM and NO, normally closed), applicable for remote centralized monitoring or alarm.
After the connection, check if the module is fitted in. If so, NC and COM are closed; if not, repress the module.
Diagram Pemasangan