Nomor Item: LY1-D20M/3(S)+1

Spesifikasi Kunci:

Model
LY1-D20M/3(S)+1

Tipe
Class II+III / Type 2+3 AC SPD

System
3P+N Three-Phase System

Protection Mode
L-N / N-PE

Protection Elements
High-Energy MOV + GDT

Voltage Options
75V / 150V / 275V / 320V AC

In / Imax
10kA / 20kA, L-N and N-PE

Pemasangan
Rel DIN 35mm

Dapatkan Penawaran Sekarang

    Compact Type 2+3 AC Surge Protection for 3P+N Systems

    LY1-D20M/3(S)+1 is a compact 3P+N pluggable Type 2+3 AC surge protective device for three-phase plus neutral systems. Its coordinated MOV and GDT structure provides L-N and N-PE surge protection with 10kA nominal discharge current and 20kA maximum discharge current.


    Class II+III / Type 2+3 downstream surge protection

    Compact 3P+N configuration with L-N and N-PE protection

    Coordinated high-energy MOV and GDT protection technology

    Pluggable modules with visual indication and optional remote contact

    Suitable Applications

    LY1-D20M/3(S)+1 is suitable for compact three-phase plus neutral systems requiring coordinated Type 2+3 surge protection in limited DIN-rail space.

    Papan Distribusi Sub

    For downstream protection in compact commercial and industrial 3P+N distribution boards.

    Industrial Control Panels

    Suitable for machinery controls, factory automation cabinets, HVAC panels, and production equipment.

    🏢

    Commercial Facilities

    Helps protect building controls, office distribution cabinets, retail systems, and sensitive commercial loads.

    Solar Inverter AC Panels

    For three-phase solar inverter AC-side panels when the selected Uc version matches the system voltage.

    FAQ

    Common questions about LY1-D20M/3(S)+1 compact 3P+N pluggable Type 2+3 AC surge protective device selection.

    What is LY1-D20M/3(S)+1 used for?

    LY1-D20M/3(S)+1 is used for downstream and final-distribution surge protection in compact three-phase plus neutral AC systems.

    What does 3P+N mean?

    3P+N means the SPD is designed for three phase conductors plus neutral, using MOV protection on the L-N paths and a GDT protection path between N-PE.

    Is LY1-D20M/3(S)+1 a Type 2 or Type 3 SPD?

    It is classified as Class II+III / Type 2+3, making it suitable for coordinated downstream and final-distribution surge protection.

    Does this SPD use MOV or GDT protection?

    It uses a coordinated MOV and GDT structure. MOV modules protect the L-N paths, while the GDT provides the N-PE protection path.

    What discharge current ratings does it provide?

    It provides 10kA nominal discharge current and 20kA maximum discharge current on both the L-N and N-PE protection paths.

    What should be confirmed before ordering?

    Confirm the nominal L-N voltage, required Uc and Up level, 3P+N wiring arrangement, 125A maximum backup-fuse coordination, conductor size, DIN-rail space, and optional remote-contact requirement.

    Data Teknis

    Electrical, mechanical, environmental, and installation data for LY1-D20M/3(S)+1 compact 3P+N pluggable Type 2+3 AC surge protective device selection.

    Parameter 75V 150V 275V 320V
    Listrik IEC
    Nominal AC Voltage Uo / Un 60V 120V 230V 230V
    Maximum Continuous Operating Voltage Uc, L-N 75V 150V 275V 320V
    Maximum Continuous Operating Voltage Uc, N-PE 255V
    Nominal Discharge Current In, L-N / N-PE 10kA / 10kA, 8/20μs
    Maximum Discharge Current Imax, L-N / N-PE 20kA / 20kA, 8/20μs
    Voltage Protection Level Up, L-N / N-PE 0.2kV / 1.5kV 0.6kV / 1.5kV 1.3kV / 1.5kV 1.5kV / 1.5kV
    Follow Current Interrupt Rating Ifi, N-PE 100 ARMS
    Response Time tA, L-N / N-PE <25ns / <100ns
    Back-Up Fuse Max. 125A gL / gG
    Short-Circuit Current Rating ISCCR, L-N 10kA
    TOV Withstand 5s UT, L-N 90V 180V 335V 335V
    TOV 120min UT, L-N 115V 230V 440V 440V
    TOV Mode Menahan Kegagalan Aman Kegagalan Aman Kegagalan Aman
    TOV Withstand 200ms UT, N-PE 1200V
    Mechanical & Environmental
    Operating Temperature Range -40°C to +70°C
    Permissible Operating Humidity 5%–95%
    Atmospheric Pressure / Altitude 80kPa–106kPa / -500m to 2000m
    Terminal Screw Torque 39.9lbf·in / 4.5Nm
    Conductor Cross Section Max. 2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Pemasangan 35mm DIN Rail, EN 60715
    Derajat Perlindungan IP20, built-in
    Bahan Perumahan Thermoplastic, UL94 V-0
    Perlindungan Termal Ya
    Operating State / Fault Indication Green: OK / Red: Defect
    Remote Contacts Optional
    RC Switching Capacity AC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max. 16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the nominal L-N voltage, required Uc and Up level, 3P+N wiring arrangement, 125A maximum backup fuse, conductor size, DIN-rail space, and optional remote contact before ordering.

    ■ Internal Configuration


    ■ Dimensions & Packaging


    ■ Connection Diagram

    Mulai Kustomisasi Sekarang

    Kami menawarkan berbagai layanan yang disesuaikan, bekerja sama dengan pelanggan kami di setiap langkah, dari desain konsep hingga pengiriman akhir.

    Produk Lainnya

    Tim kami selalu dipandu oleh kebutuhan pelanggan kami, memberikan konsultasi dan dukungan profesional untuk memastikan kepuasan Anda.

    APA YANG TIDAK BISA ANDA TEMUKAN?

    Bicaralah Dengan Penjualan Kami

    Kami tahu bahwa setiap bisnis unik, jadi kami menawarkan layanan kustom untuk memastikan bahwa produk kami cocok sempurna dengan kebutuhan spesifik Anda:

    • Brosur komprehensif yang dapat Anda unduh
    • Pengalaman pabrik selama 15 tahun
    • Pengiriman cepat
    • OEM&ODM
    • Harga rendah
    • MQQ kecil

    KIRIM KEPADA KAMI EMAIL

    devin@cnspd.com

    Hubungi Kami

    Kami terus menilai dan meningkatkan proses kami untuk memastikan bahwa kami memberikan produk listrik yang paling efisien dan dapat diandalkan di pasar.