Articolo n: LY1-B25/1(S)+1

Key Specifications:

Modello
LY1-B25/1(S)+1

Tipo
Class I+II / Type 1+2 AC SPD

Pali
1P+N Monoblock Design

Network System
TT / TN-S

Modalità di protezione
L-N / N-PE

Iimp
25kA / 50kA, 10/350μs

In / Imax
25kA / 50kA In, 100kA Imax

Montaggio
35mm DIN Rail

Cita ora

    High-Energy Type 1+2 AC Surge Protection for 1P+N Systems

    LY1-B25/1(S)+1 is a monoblock 1P+N Type 1+2 AC surge protective device designed for TT and TN-S low-voltage distribution systems. It combines high-energy MOV and GDT protection elements to help protect incoming AC power lines from lightning surges and transient overvoltage.


    Class I+II / Type 1+2 AC SPD for main distribution board protection

    1P+N protection design for TT and TN-S network systems

    High-energy MOV and GDT elements for L-N and N-PE protection

    35mm DIN-rail mounting for main distribution boards and power panels

    Suitable Applications

    LY1-B25/1(S)+1 is suitable for TT and TN-S AC power systems where Type 1+2 surge protection is required at the incoming power side or main distribution level.

    Main Distribution Boards

    For incoming surge protection in single-phase plus neutral AC distribution boards.

    🏠

    Residential Power Systems

    Suitable for residential service panels where 1P+N surge protection is required.

    🏢

    Edifici commerciali

    Helps protect commercial low-voltage power systems from lightning-induced surges.

    Power Panels

    For control cabinets, combiner boxes, and low-voltage AC power panels.

    FAQ

    Common questions about LY1-B25/1(S)+1 1P+N monoblock AC surge protective device selection and application.

    What is LY1-B25/1(S)+1 used for?

    LY1-B25/1(S)+1 is used for Type 1+2 AC surge protection in TT and TN-S systems. It protects L-N and N-PE paths at the main distribution board or incoming power side.

    What does 1P+N mean?

    1P+N means the SPD is designed for single-phase plus neutral systems, with protection paths between L-N and N-PE depending on the system design.

    What surge ratings does this SPD provide?

    The product provides 25kA / 50kA impulse discharge current Iimp, 25kA / 50kA nominal discharge current In, 100kA maximum discharge current Imax, and 50kA total discharge current Itotal.

    What is the role of MOV and GDT in this SPD?

    The MOV helps clamp transient overvoltage quickly, while the GDT is used for high-energy discharge, especially in the N-PE protection path.

    Does this model support remote signalling?

    Yes. The “S” version can include optional remote contact for SPD status monitoring. Please confirm this requirement before ordering.

    What should be confirmed before ordering?

    Please confirm system voltage, TT or TN-S network system, protection mode, backup fuse, installation space, wiring cross-section, and remote signalling requirement before ordering.

    Dati tecnici

    Detailed electrical, mechanical, and installation data for LY1-B25/1(S)+1 1P+N monoblock AC surge protective device selection.

    Parametro150V275V320V385V
    Nominal AC Voltage Uo / Un120V230V230V230V
    Maximum Continuous Operating Voltage Uc (L-N)150V275V320V385V
    Maximum Continuous Operating Voltage Uc (N-PE)255V
    Nominal Discharge Current In, 8/20μs (L-N / N-PE)25kA / 50kA
    Maximum Discharge Current Imax, 8/20μs100kA
    Impulse Discharge Current Iimp, 10/350μs (L-N / N-PE)25kA / 50kA
    Total Discharge Current Itotal, 10/350μs50kA
    Specific Energy W/R (L-N / N-PE)156 kJ / Ω / 625 kJ / Ω
    Charge Q (L-N / N-PE)12,5 As / 25 As
    Voltage Protection Level Up (L-N / N-PE)1.0kV / 1.5kV1.5kV / 1.5kV1.6kV / 1.5kV1.8kV / 1.5kV
    Follow Current Interrupt Rating Ifi (N-PE)100 ARMI
    Response Time tA (L-N / N-PE)< 25 ns / < 100 ns
    Back-Up Fuse Max.315A gL / gG
    Short-Circuit Current Rating ISCCR (L-N)50kA
    TOV Withstand 5s UT (L-N)180V335V335V335V
    TOV 120min UT (L-N)230V440V440V440V
    TOV Withstand 200ms UT (N-PE)1200V
    Temperatura di esercizio-40°C to +70°C
    Conductor Cross Section35mm² solid / stranded, 25mm² flexible
    Coppia di serraggio delle viti dei terminali4.5 Nm
    Montaggio35mm DIN Rail, EN 60715
    Grado di protezioneIP20, built-in
    Materiale dell'alloggiamentoThermoplastic, UL 94 V-0
    Stato di funzionamento / Indicazione di guastoGreen: OK / Red: Defect
    Remote ContactOpzionale
    Selection Note:
    Please confirm system voltage, TT or TN-S network system, L-N / N-PE protection mode, backup fuse, installation space, wiring cross-section, and remote signalling requirement before ordering.

    Configurazione interna


    Dimensioni e imballaggio


    Diagramma di collegamento

    Iniziare a personalizzare ora

    Offriamo una gamma completa di servizi personalizzati, lavorando a stretto contatto con i nostri clienti in ogni fase del processo, dalla progettazione alla consegna finale.

    Altri prodotti

    Il nostro team è sempre guidato dalle esigenze dei nostri clienti, fornendo consulenza e assistenza professionale per garantire la vostra soddisfazione.

    TUTTO CIÒ CHE NON SEI RIUSCITO A TROVARE.

    Parlate con le nostre vendite

    Sappiamo che ogni azienda è unica, quindi offriamo servizi personalizzati per garantire che i nostri prodotti si adattino perfettamente alle vostre esigenze specifiche:

    • Una brochure completa da scaricare
    • 15 anni di esperienza in fabbrica
    • Consegna veloce
    • OEM&ODM
    • Prezzo basso
    • Piccolo MQQ

    INVIATECI UN'E-MAIL

    devin@cnspd.com

    Contatto

    Valutiamo e miglioriamo costantemente i nostri processi per garantire la fornitura dei prodotti elettrici più efficienti e affidabili del mercato.