LY1-C40PV/2(S) 1000V Pluggable Single-Pole SPD

LY1-C40PV/2(S) 1000V Pluggable Single-Pole SPD

Short Description:

Class I Class II Type 1 Type 2
Location of Use: Sub-Distribution Boards
Mode of Protection: (DC+) – PE, (DC-) – PE
Surge Ratings: In = 20 kA (8/20 μs)
IEC/EN/UL Category: Class I+II / Type 1+2
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-31:2018 EN 50539-11:2013+A1:2014


Product Detail

Product Tags

Technical Data

IEC Electrical 1000
Nominal AC Voltage                                               Uo/ Un 1000 V
Maximum Continuous Operating Voltage (DC)         Uc 1000 V
Nominal Discharge Current (8/20 μs)                        In 20 kA
Maximum Discharge Current (8/20 μs)                     Imax 40 kA
Impulse Discharge Current (10/350 μs)                    Iimp 6.25 kA
Voltage Protection Level Up 3.6 kV
Response Time tA < 25 ns
Back-Up Fuse (max) 125 A gL / gG
Short-Circuit Current Rating (AC)                            ISCCR 25 kA / 50 kA
Mechanical & Environmental
Operating Temperature Range Ta -40ºF to +158ºF [-40ºC to +70ºC]
Permissible Operating Humidity RH 5%...95%
Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m.....2000 m
Terminal Screw Torque Mmax 39.9 Ibf ·in [4.5 Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35 mm2  (Solid, Stranded) / 25 mm2(Flexible)
Mounting 35 mm DIN Rail, EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection Yes
Operating State / Fault Indication Green ok / Red defect
Remote Contacts (RC)RC Switching CapacityRC Conductor Cross Section (max) OptionalAC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A16 AWG (Solid) / 1.5 mm2(Solid)

Internal Configuration

2p

Dimensions & Packaging

sda14238

Connection Diagram

asd

  • Previous:
  • Next:

  • Write your message here and send it to us

    PRODUCT CATEGORIES