Technical Parameter
Model |
LY1-D20 |
Test standard |
IEC/EN 61643-11;GB18802.11 |
IEC test classification |
T2/Class II |
Maximum continuous operating voltage Uc |
275V/385V AC |
Nominal discharge current (8/20µs) |
10kA |
Maximum discharge current(8/20µs) |
20kA |
Voltage protection level Up |
≤1.2kV(275V AC ) ≤1.5kV(385V AC) |
Response time Ta |
25ns |
Poles |
1P 2P 3P 4P 1P+N-PE 3P+N-PE |
Fuse or circuit breaker selection(A) |
32A |
Connecting cable |
4mm2(L-N); 6mm2(PE) |
Method of Installation |
35mm Din Rail |
Type of remote signaling contact Switching contact(Optional) |
C+NC: Normally closed C+NO: Normally open C: Common contact |
Switching capacity |
AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A |
Cross-sectional area for remote signal contact |
Max. 1.5mm2 solid / flexible |
Operating temperature range |
40°C…+80°C |
Shell material |
UL94-V0 fireproof material |