Nº do artigo: LY1-C40/3(S)+1

Key Specifications:

Modelo
LY1-C40/3(S)+1

Tipo
Class II / Type 2 AC SPD

Postes
3P+N Pluggable Design

Modo de proteção
L-N / N-PE

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
20kA / 40kA, 8/20μs

Protection Elements
MOV + GDT

Montagem
35mm DIN Rail

Citar agora

    Coordinated Type 2 AC Surge Protection for 3P+N Systems

    LY1-C40/3(S)+1 is a pluggable 3P+N Type 2 AC surge protective device designed for three-phase plus neutral distribution systems. Coordinated MOV and GDT protection paths help limit transient overvoltage between L-N and N-PE while providing fast response and reliable protection for multi-pole AC circuits.


    3P+N Type 2 AC SPD for three-phase distribution boards

    20kA nominal and 40kA maximum discharge current

    MOV protection for L-N and GDT protection for N-PE coordination

    Replaceable pluggable modules with optional remote status contact

    Suitable Applications

    LY1-C40/3(S)+1 is suitable for three-phase plus neutral AC systems requiring coordinated Type 2 surge protection at the sub-distribution or equipment-panel level.

    Distribution Boards

    For coordinated L-N and N-PE protection in three-phase plus neutral distribution boards.

    Industrial Control Panels

    Suitable for industrial control cabinets, machinery panels, HVAC systems, and automation equipment.

    🏢

    Edifícios comerciais

    Helps protect three-phase building power systems from switching surges and lightning-induced overvoltage.

    Solar AC Panels

    For the AC side of solar installations when voltage rating and 3P+N protection design match the system.

    FAQ

    Common questions about LY1-C40/3(S)+1 pluggable 3P+N Type 2 AC surge protective device selection.

    What is LY1-C40/3(S)+1 used for?

    It is used for Type 2 surge protection in three-phase plus neutral AC distribution systems, with coordinated protection between L-N and N-PE.

    What does 3P+N mean?

    3P+N means the SPD is designed for three-phase plus neutral systems, with L-N protection across the phases and coordinated N-PE protection.

    Why does this model use MOV and GDT protection?

    MOV elements provide fast voltage clamping on the L-N paths, while the GDT supports coordinated discharge on the N-PE path with low leakage during normal operation.

    What discharge current ratings does it provide?

    The SPD provides 20kA nominal discharge current In and 40kA maximum discharge current Imax for both L-N and N-PE protection paths.

    What voltage options are available?

    L-N maximum continuous operating voltage options include 75V, 150V, 275V, 320V, 385V, and 440V AC. The N-PE continuous operating voltage is 255V.

    What should be confirmed before ordering?

    Confirm the system voltage, 3P+N arrangement, L-N and N-PE protection mode, backup fuse, wiring cross-section, DIN-rail space, and remote contact requirement.

    Dados técnicos

    Electrical, mechanical, and installation data for LY1-C40/3(S)+1 pluggable 3P+N Type 2 AC surge protective device selection.

    Parâmetro75V150V275V320V385V440V
    IEC Elétrico
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc, L-N75V150V275V320V385V440V
    Maximum Continuous Operating Voltage Uc, N-PE255V
    Nominal Discharge Current In, L-N / N-PE20kA / 20kA, 8/20μs
    Maximum Discharge Current Imax, L-N / N-PE40kA / 40kA, 8/20μs
    Voltage Protection Level Up, L-N / N-PE0.4kV / 1.5kV1.0kV / 1.5kV1.5kV / 1.5kV1.6kV / 1.5kV1.8kV / 1.5kV2.0kV / 1.5kV
    Follow Current Interrupt Rating Ifi, N-PE100 ARMAS
    Response Time tA, L-N / N-PE<25ns / <100ns
    Back-Up Fuse Max.315A / 250A gG
    Short-Circuit Current Rating ISCCR, L-N25kA / 50kA
    TOV Withstand 5s UT, L-N90V180V335V335V335V580V
    TOV 120min UT, L-N115V230V440V440V440V765V
    TOV ModeSuportarSuportarFalha de segurançaFalha de segurançaFalha de segurançaFalha de segurança
    TOV Withstand 200ms UT, N-PE1200V
    Mecânica e ambiente
    Gama de temperaturas de funcionamento-40°C to +70°C
    Humidade de funcionamento admissível5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Torque do parafuso do terminal39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Montagem35mm DIN Rail, EN 60715
    Grau de proteçãoIP20, built-in
    Material da caixaThermoplastic, UL94 V-0
    Proteção térmicaSim
    Estado de funcionamento / Indicação de avariaGreen: OK / Red: Defect
    Remote ContactsOpcional
    Capacidade de comutação RCAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the required L-N voltage rating, 3P+N system arrangement, N-PE protection, backup fuse, wiring size, DIN-rail space, and optional remote contact before ordering.

    Configuração interna


    ■ Dimensões e embalagem


    Diagrama de ligação

    Comece a personalizar agora

    Oferecemos uma gama completa de serviços personalizados, trabalhando em estreita colaboração com os nossos clientes em todas as fases do processo, desde a conceção até à entrega final.

    Outros&Produtos

    A nossa equipa é sempre guiada pelas necessidades dos nossos clientes, fornecendo aconselhamento profissional e apoio para garantir a sua satisfação.

    QUALQUER COISA QUE NÃO CONSEGUISTE ENCONTRAR?

    Fale com os nossos comerciais

    Sabemos que cada empresa é única, por isso oferecemos serviços personalizados para garantir que os nossos produtos correspondem perfeitamente às suas necessidades específicas:

    • Brochura completa que pode ser descarregada
    • 15 anos de experiência na fábrica
    • Entrega rápida
    • OEM&ODM
    • Preço baixo
    • Pequena MQQ

    ENVIAR-NOS UMA MENSAGEM DE CORREIO ELECTRÓNICO

    devin@cnspd.com

    Contactar-nos

    Avaliamos e melhoramos constantemente os nossos processos para garantir que estamos a fornecer os produtos eléctricos mais eficientes e fiáveis do mercado.