Numéro d'article : LY1-D20/2(S)

Key Specifications:

Modèle
LY1-D20/2(S)

Type
Class II+III / Type 2+3 AC SPD

Pole Configuration
2-Pole Pluggable Design

Mode de protection
L-PE / N-PE

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
10kA / 20kA, 8/20μs

Back-Up Fuse
125A gL / gG Max.

Montage
35mm DIN Rail

Citer maintenant

    Compact Type 2+3 AC Surge Protection for Two-Pole Circuits

    LY1-D20/2(S) is a two-pole pluggable Type 2+3 AC surge protective device designed for sub-distribution boards and final equipment circuits. Its high-energy MOV modules provide dual-path surge suppression through L-PE and N-PE, with 10kA nominal discharge current and 20kA maximum discharge current.


    Class II+III / Type 2+3 protection for downstream AC circuits

    Two-pole design with L-PE and N-PE protection paths

    10kA nominal and 20kA maximum discharge current

    Replaceable cartridges with visual indication and optional remote contact

    Suitable Applications

    LY1-D20/2(S) is suitable for downstream and final-distribution AC circuits requiring compact two-pole Type 2+3 surge protection.

    Tableaux de sous-distribution

    For downstream surge protection in residential, commercial, and light-industrial panels.

    🏠

    Residential Consumer Units

    Suitable for household distribution systems requiring protection of line and neutral paths.

    Small Machinery Panels

    Helps protect control equipment, compact machines, and electronic loads from transient overvoltage.

    Solar Inverter AC Boxes

    For AC-side solar inverter boxes when the selected Uc version matches the system voltage.

    FAQ

    Common questions about LY1-D20/2(S) two-pole pluggable Type 2+3 AC surge protective device selection and installation.

    What is LY1-D20/2(S) used for?

    LY1-D20/2(S) is used for downstream surge protection in sub-distribution boards and final equipment circuits. It provides two protection paths for limiting transient overvoltage before it reaches connected loads.

    Is LY1-D20/2(S) a single-pole or two-pole SPD?

    LY1-D20/2(S) is a two-pole surge protective device. The existing page title describing it as single-pole should be changed to two-pole.

    Is LY1-D20/2(S) a Type 2 or Type 3 SPD?

    LY1-D20/2(S) is classified as Class II+III / Type 2+3, making it suitable for coordinated downstream and final-distribution surge protection.

    What discharge current ratings does it provide?

    It provides 10kA nominal discharge current In and 20kA maximum discharge current Imax, based on the 8/20μs current waveform.

    What voltage options are available?

    Available maximum continuous operating voltage options are 75V, 150V, 275V, 320V, 385V, and 440V AC. Select the version according to the nominal system voltage.

    What should be confirmed before ordering?

    Confirm the nominal system voltage, required Uc and Up level, two-pole protection arrangement, 125A maximum backup-fuse coordination, conductor size, DIN-rail space, and remote-contact requirement.

    Données techniques

    Electrical, mechanical, environmental, and installation data for LY1-D20/2(S) two-pole pluggable Type 2+3 AC surge protective device selection.

    Paramètres75V150V275V320V385V440V
    Électrique IEC
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc75V150V275V320V385V440V
    Nominal Discharge Current In, 8/20μs10kA
    Maximum Discharge Current Imax, 8/20μs20kA
    Voltage Protection Level Up0.2kV0.6kV1.3kV1.5kV1.5kV1.8kV
    Response Time tA<25ns
    Back-Up Fuse Max.125A gL / gG
    Short-Circuit Current Rating ISCCR10kA
    TOV Withstand 5s UT90V180V335V335V335V580V
    TOV 120min UT115V230V440V440V440V765V
    TOV ModeRésistanceRésistanceDéfaut de sécuritéDéfaut de sécuritéDéfaut de sécuritéDéfaut de sécurité
    Mécanique et environnement
    Plage de température de fonctionnement-40°F to +158°F [-40°C to +70°C]
    Humidité de fonctionnement admissible5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Couple de serrage de la vis de fixation39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Montage35mm DIN Rail, EN 60715
    Degré de protectionIP20, built-in
    Matériau du boîtierThermoplastic, UL94 V-0
    Protection thermiqueOui
    État de fonctionnement / Indication de défautGreen: OK / Red: Defect
    Remote ContactsEn option
    Capacité de commutation RCAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the nominal system voltage, required Uc and Up level, two-pole protection arrangement, 125A maximum backup fuse, conductor size, DIN-rail space, and optional remote contact before ordering.

    ■ Configuration interne


    ■ Dimensions et emballage


    ■ Schéma de connexion

    Commencez à personnaliser maintenant

    Nous offrons une gamme complète de services personnalisés, en travaillant en étroite collaboration avec nos clients à chaque étape, de la conception à la livraison finale.

    Autres&Produits

    Notre équipe est toujours guidée par les besoins de nos clients, fournissant une consultation et un soutien professionnels pour assurer votre satisfaction.

    TOUT CE QUE VOUS N'AVEZ PAS PU TROUVER?

    Parlez avec nos vendeurs

    Nous savons que chaque entreprise est unique, c'est pourquoi nous proposons des services personnalisés afin de garantir que nos produits répondent parfaitement à vos besoins spécifiques :

    • Brochure complète à télécharger
    • 15 ans d'expérience en usine
    • Livraison rapide
    • OEM&ODM
    • Prix bas
    • Petit MQQ

    ENVOYEZ-NOUS UN COURRIEL

    devin@cnspd.com

    Nous contacter

    Nous évaluons et améliorons constamment nos processus pour nous assurer que nous fournissons les produits électriques les plus efficaces et les plus fiables du marché.