Articolo n: LY1-D20/2(S)

Key Specifications:

Modello
LY1-D20/2(S)

Tipo
Class II+III / Type 2+3 AC SPD

Pole Configuration
2-Pole Pluggable Design

Modalità di protezione
L-PE / N-PE

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
10kA / 20kA, 8/20μs

Back-Up Fuse
125A gL / gG Max.

Montaggio
35mm DIN Rail

Cita ora

    Compact Type 2+3 AC Surge Protection for Two-Pole Circuits

    LY1-D20/2(S) is a two-pole pluggable Type 2+3 AC surge protective device designed for sub-distribution boards and final equipment circuits. Its high-energy MOV modules provide dual-path surge suppression through L-PE and N-PE, with 10kA nominal discharge current and 20kA maximum discharge current.


    Class II+III / Type 2+3 protection for downstream AC circuits

    Two-pole design with L-PE and N-PE protection paths

    10kA nominal and 20kA maximum discharge current

    Replaceable cartridges with visual indication and optional remote contact

    Suitable Applications

    LY1-D20/2(S) is suitable for downstream and final-distribution AC circuits requiring compact two-pole Type 2+3 surge protection.

    Schede di sottodistribuzione

    For downstream surge protection in residential, commercial, and light-industrial panels.

    🏠

    Residential Consumer Units

    Suitable for household distribution systems requiring protection of line and neutral paths.

    Small Machinery Panels

    Helps protect control equipment, compact machines, and electronic loads from transient overvoltage.

    Solar Inverter AC Boxes

    For AC-side solar inverter boxes when the selected Uc version matches the system voltage.

    FAQ

    Common questions about LY1-D20/2(S) two-pole pluggable Type 2+3 AC surge protective device selection and installation.

    What is LY1-D20/2(S) used for?

    LY1-D20/2(S) is used for downstream surge protection in sub-distribution boards and final equipment circuits. It provides two protection paths for limiting transient overvoltage before it reaches connected loads.

    Is LY1-D20/2(S) a single-pole or two-pole SPD?

    LY1-D20/2(S) is a two-pole surge protective device. The existing page title describing it as single-pole should be changed to two-pole.

    Is LY1-D20/2(S) a Type 2 or Type 3 SPD?

    LY1-D20/2(S) is classified as Class II+III / Type 2+3, making it suitable for coordinated downstream and final-distribution surge protection.

    What discharge current ratings does it provide?

    It provides 10kA nominal discharge current In and 20kA maximum discharge current Imax, based on the 8/20μs current waveform.

    What voltage options are available?

    Available maximum continuous operating voltage options are 75V, 150V, 275V, 320V, 385V, and 440V AC. Select the version according to the nominal system voltage.

    What should be confirmed before ordering?

    Confirm the nominal system voltage, required Uc and Up level, two-pole protection arrangement, 125A maximum backup-fuse coordination, conductor size, DIN-rail space, and remote-contact requirement.

    Dati tecnici

    Electrical, mechanical, environmental, and installation data for LY1-D20/2(S) two-pole pluggable Type 2+3 AC surge protective device selection.

    Parametro75V150V275V320V385V440V
    IEC Elettrico
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc75V150V275V320V385V440V
    Nominal Discharge Current In, 8/20μs10kA
    Maximum Discharge Current Imax, 8/20μs20kA
    Voltage Protection Level Up0.2kV0.6kV1.3kV1.5kV1.5kV1.8kV
    Response Time tA<25ns
    Back-Up Fuse Max.125A gL / gG
    Short-Circuit Current Rating ISCCR10kA
    TOV Withstand 5s UT90V180V335V335V335V580V
    TOV 120min UT115V230V440V440V440V765V
    TOV ModeResistereResistereFallimento sicuroFallimento sicuroFallimento sicuroFallimento sicuro
    Meccanico e ambientale
    Intervallo di temperatura operativa-40°F to +158°F [-40°C to +70°C]
    Umidità operativa consentita5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Coppia di serraggio delle viti dei terminali39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Montaggio35mm DIN Rail, EN 60715
    Grado di protezioneIP20, built-in
    Materiale dell'alloggiamentoThermoplastic, UL94 V-0
    Protezione termica
    Stato di funzionamento / Indicazione di guastoGreen: OK / Red: Defect
    Remote ContactsOpzionale
    Capacità di commutazione RCAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the nominal system voltage, required Uc and Up level, two-pole protection arrangement, 125A maximum backup fuse, conductor size, DIN-rail space, and optional remote contact before ordering.

    Configurazione interna


    Dimensioni e imballaggio


    Diagramma di collegamento

    Iniziare a personalizzare ora

    Offriamo una gamma completa di servizi personalizzati, lavorando a stretto contatto con i nostri clienti in ogni fase del processo, dalla progettazione alla consegna finale.

    Altri prodotti

    Il nostro team è sempre guidato dalle esigenze dei nostri clienti, fornendo consulenza e assistenza professionale per garantire la vostra soddisfazione.

    TUTTO CIÒ CHE NON SEI RIUSCITO A TROVARE.

    Parlate con le nostre vendite

    Sappiamo che ogni azienda è unica, quindi offriamo servizi personalizzati per garantire che i nostri prodotti si adattino perfettamente alle vostre esigenze specifiche:

    • Una brochure completa da scaricare
    • 15 anni di esperienza in fabbrica
    • Consegna veloce
    • OEM&ODM
    • Prezzo basso
    • Piccolo MQQ

    INVIATECI UN'E-MAIL

    devin@cnspd.com

    Contatto

    Valutiamo e miglioriamo costantemente i nostri processi per garantire la fornitura dei prodotti elettrici più efficienti e affidabili del mercato.