Articolo n: LY1-D20M/4(S)

Key Specifications:

Modello
LY1-D20M/4(S)

Tipo
Class II+III / Type 2+3 AC SPD

Pole Configuration
4P / 3P+N Compact Pluggable Design

Modalità di protezione
L-PE / N-PE

Protection Element
High-Energy MOV

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
10kA / 20kA, 8/20μs

Montaggio
35mm DIN Rail

Cita ora

    Compact Type 2+3 AC Surge Protection for Three-Phase Systems

    LY1-D20M/4(S) is a compact four-pole pluggable Type 2+3 AC surge protective device designed for three-phase plus neutral distribution systems. Its high-energy MOV modules provide coordinated surge limitation across L1, L2, L3, and N, with 10kA nominal discharge current and 20kA maximum discharge current.


    Class II+III / Type 2+3 downstream surge protection

    Compact 4P design for L1, L2, L3, and neutral protection

    10kA nominal and 20kA maximum discharge current

    Individually replaceable cartridges with optional remote contact

    Suitable Applications

    LY1-D20M/4(S) is suitable for compact three-phase plus neutral systems requiring coordinated Type 2+3 surge protection in limited DIN-rail space.

    Three-Phase Distribution Boards

    For compact commercial and industrial three-phase plus neutral distribution panels.

    Industrial Control Panels

    Suitable for machinery controls, automation cabinets, HVAC panels, and factory equipment.

    🏢

    Commercial Facilities

    Helps protect building electrical cabinets, retail facilities, offices, and commercial equipment.

    Solar Inverter AC Panels

    For three-phase solar inverter AC-side panels when the selected Uc rating matches the system voltage.

    FAQ

    Common questions about LY1-D20M/4(S) compact four-pole pluggable Type 2+3 AC surge protective device selection.

    What is LY1-D20M/4(S) used for?

    LY1-D20M/4(S) is used for downstream and final-distribution surge protection in three-phase plus neutral AC systems. It provides coordinated protection for L1, L2, L3, and neutral conductors.

    What does the four-pole configuration protect?

    The four-pole configuration protects the three phase conductors and the neutral conductor in a three-phase four-wire electrical system.

    Is LY1-D20M/4(S) a Type 2 or Type 3 SPD?

    LY1-D20M/4(S) is classified as Class II+III / Type 2+3, making it suitable for coordinated downstream and final-distribution surge protection.

    Does this product use MOV or GDT protection?

    The verified product specifications identify high-energy MOV protection. The previous description referring to the complete product as a neon-gas GDT SPD should be removed.

    What discharge current ratings does it provide?

    It provides 10kA nominal discharge current In and 20kA maximum discharge current Imax, based on an 8/20μs current waveform.

    Can each protection cartridge be replaced separately?

    Yes. The pluggable design allows individual protection cartridges to be inspected or replaced without removing the permanently wired base.

    Dati tecnici

    Electrical, mechanical, environmental, and installation data for LY1-D20M/4(S) compact four-pole pluggable Type 2+3 AC surge protective device selection.

    Parametro75V150V275V320V385V440V
    IEC Elettrico
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc75V150V275V320V385V440V
    Nominal Discharge Current In, 8/20μs10kA
    Maximum Discharge Current Imax, 8/20μs20kA
    Voltage Protection Level Up0.2kV0.6kV1.3kV1.5kV1.5kV1.8kV
    Response Time tA<25ns
    Back-Up Fuse Max.125A gL / gG
    Short-Circuit Current Rating ISCCR10kA
    TOV Withstand 5s UT90V180V335V335V335V580V
    TOV 120min UT115V230V440V440V440V765V
    TOV ModeResistereResistereFallimento sicuroFallimento sicuroFallimento sicuroFallimento sicuro
    Meccanico e ambientale
    Intervallo di temperatura operativa-40°C to +70°C
    Umidità operativa consentita5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Coppia di serraggio delle viti dei terminali39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Montaggio35mm DIN Rail, EN 60715
    Grado di protezioneIP20, built-in
    Materiale dell'alloggiamentoThermoplastic, UL94 V-0
    Protezione termica
    Stato di funzionamento / Indicazione di guastoGreen: OK / Red: Defect
    Remote ContactsOpzionale
    Capacità di commutazione RCAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the nominal system voltage, required Uc and Up level, four-pole wiring arrangement, 125A maximum backup fuse, conductor size, available DIN-rail space, and optional remote contact before ordering.

    Configurazione interna


    Dimensioni e imballaggio


    Diagramma di collegamento

    Iniziare a personalizzare ora

    Offriamo una gamma completa di servizi personalizzati, lavorando a stretto contatto con i nostri clienti in ogni fase del processo, dalla progettazione alla consegna finale.

    Altri prodotti

    Il nostro team è sempre guidato dalle esigenze dei nostri clienti, fornendo consulenza e assistenza professionale per garantire la vostra soddisfazione.

    TUTTO CIÒ CHE NON SEI RIUSCITO A TROVARE.

    Parlate con le nostre vendite

    Sappiamo che ogni azienda è unica, quindi offriamo servizi personalizzati per garantire che i nostri prodotti si adattino perfettamente alle vostre esigenze specifiche:

    • Una brochure completa da scaricare
    • 15 anni di esperienza in fabbrica
    • Consegna veloce
    • OEM&ODM
    • Prezzo basso
    • Piccolo MQQ

    INVIATECI UN'E-MAIL

    devin@cnspd.com

    Contatto

    Valutiamo e miglioriamo costantemente i nostri processi per garantire la fornitura dei prodotti elettrici più efficienti e affidabili del mercato.