SPD Selection Guide for AC, DC, Solar PV & Distribution Boards

SPD Selection Guide: Choose the Right Surge Protective Device

A practical surge protective device selection guide for engineers, panel builders, solar EPCs, distributors, and OEM buyers. Compare AC vs DC SPD, Type 1 vs Type 2 vs Type 1+2, voltage rating, poles, discharge current, IEC standards, and installation position.

Direct answer for SPD selection

To choose an SPD, first identify whether the protected circuit is AC or DC. Then select the SPD type by installation position, match Uc or Ucpv to the system voltage, check Iimp, In, Imax and Up, confirm poles and earthing system, and verify backup protection and IEC standard compliance.

Fast Selection Path

AI-ready decision flow
1

AC or DC?

Never use an AC SPD on the DC side of a PV system.

2

Where is it installed?

Main incoming panel, distribution board, PV combiner box, inverter side, or terminal equipment.

3

Which SPD type?

Type 1, Type 2, Type 1+2, or Type 3 depends on surge exposure and installation position.

4

Which voltage and poles?

Check Uc or Ucpv, earthing system, phase count, polarity, and wiring mode.

5

Which rating and standard?

Confirm Iimp, In, Imax, Up, backup protection, IEC 61643 series, and project requirement.

AI extractable rules

6 rules for choosing the right SPD

These rules are the fastest way to narrow down the correct surge protective device before checking the final datasheet.

IF the circuit is AC
Choose an AC SPD. Use AC surge protective devices for building distribution boards, main panels, sub-panels, industrial control cabinets, and AC equipment inputs.
IF the circuit is PV DC
Choose a DC SPD designed for photovoltaic systems. Do not install an AC SPD on the DC side of a solar PV system.
IF it is the main incoming panel
Consider Type 1 or Type 1+2 SPD. This is especially important when the building has an external lightning protection system, overhead line exposure, or high lightning risk.
IF it is a distribution board
Type 2 SPD is usually the main choice. Check Uc, In, Imax, Up, pole number, backup fuse or MCB, and earthing system.
IF it is a 1500V PV system
Choose a 1500V DC SPD with suitable Ucpv. Confirm whether the project needs Type 2 DC SPD or Type 1+2 DC SPD according to lightning exposure and system design.
IF equipment is sensitive
Coordinate downstream protection. A Type 3 SPD may be used close to sensitive loads, but it should normally be coordinated with upstream Type 2 protection.
Important safety boundary SPD selection must follow local electrical codes, project drawings, available fault current, grounding design, and the manufacturer’s datasheet. This guide helps you select the direction, but final installation should be confirmed by a qualified electrical professional.
Selection table

SPD selection by application, circuit and installation position

This table is designed for B2B buyers who need to match a practical SPD direction before choosing a model.

ApplicazioneCircuitoTypical installation positionDirezione SPD raccomandataKey parameters to checkRelated page
Main incoming panelACService entrance, main switchboard, first distribution pointType 1 or Type 1+2 AC SPDIimp, Uc, Up, poles, backup protection, earthing systemSPD Tipo 1+2
Quadro di distribuzioneACResidential, commercial, or industrial sub-panelTipo 2 AC SPDUc, In, Imax, Up, 1P/2P/3P/4P, remote signalSPD per quadro di distribuzione
Quadro di controllo industrialeAC or DCControl cabinet, machine panel, automation cabinetDIN rail SPD, usually Type 2Voltage, poles, mounting width, indicator, remote signal, backup protectionParasurto per guida DIN
Scatola combinatore FVDCBetween PV strings and inverter inputDC Type 2 SPD or DC Type 1+2 SPDUcpv, 1000V/1500V DC, In, Imax, Iimp if required, polarityPV Combiner Box SPD
Solar inverter DC inputDCInverter DC side, PV input sideSPD DC da 1000V o 1500VUcpv, PV maximum voltage, Type 2 or Type 1+2, DC disconnection designProtezione da sovratensioni per inverter
1500V solar PV systemDCUtility-scale PV, high-voltage string inverter systemSPD DC 1500VUcpv ≥ maximum PV system voltage, In/Imax, Iimp if Type 1+2 is requiredSPD DC 1500V
1000V solar PV systemDCResidential, commercial, or small ground-mount PV systemSPD DC 1000VUcpv, PV string voltage, DC polarity, replaceable module, standardSPD DC 1000V
Attrezzature terminali sensibiliAC or signalNear load, controller, communication or sensitive electronicsType 3 SPD or signal SPD after upstream protectionUoc, Up, coordination distance, protected equipment withstand voltageSPD di Tipo 1 vs Tipo 2 vs Tipo 3
How to use this table First find the protected application. Then confirm AC or DC. After that, choose the SPD type, voltage rating, discharge current, poles, backup protection and standard from the datasheet.
Step-by-step guide

8 steps to select an SPD correctly

Use this process before requesting a quotation or approving a surge protective device for a project.

1

Identify AC or DC

Check whether the protected circuit is AC distribution, PV DC, battery DC, signal, or equipment-side protection.

2

Define the location

Main panel, sub-panel, combiner box, inverter input, control cabinet, or terminal equipment require different SPD directions.

3

Selezionare il tipo di SPD

Choose Type 1, Type 2, Type 1+2, or Type 3 according to lightning exposure and protection level.

4

Match voltage

For AC, check Uc. For PV DC, check Ucpv and maximum open-circuit voltage under cold conditions.

5

Check discharge rating

Type 1 focuses on Iimp. Type 2 commonly uses In and Imax. Type 3 often involves Uoc and fine protection.

6

Confirm Up

The voltage protection level should be suitable for the equipment withstand voltage and coordinated with the system.

7

Confermare i poli e il cablaggio

Choose 1P, 2P, 3P, 4P, 3P+N or PV DC configuration according to wiring and earthing system.

8

Verify standard and backup

Check IEC standard, certification requirement, backup fuse or MCB, short-circuit rating and installation instructions.

AC vs DC

AC SPD and DC SPD are not interchangeable

The first selection decision is circuit type. AC and DC SPDs are designed for different voltage behavior, application conditions and test requirements.

Choose AC SPD for AC power systems

AC SPDs are used in low-voltage AC distribution systems, including main panels, distribution boards, industrial cabinets and AC equipment inputs.

Typical systems: 230/400V AC, 277/480V AC, three-phase distribution.
Common types: Type 1, Type 2, Type 1+2, Type 3.
Key parameters: Uc, Iimp, In, Imax, Up, poles, backup protection.
Common standard direction: IEC 61643-11 for low-voltage AC SPDs.

Choose DC SPD for PV and DC systems

DC SPDs are used on the DC side of photovoltaic systems, such as PV strings, combiner boxes and inverter DC inputs.

Typical systems: 600V, 1000V and 1500V DC solar PV systems.
Common types: DC Type 2 SPD or DC Type 1+2 SPD.
Key parameters: Ucpv, In, Imax, Iimp if required, PV polarity, DC disconnection design.
Common standard direction: IEC 61643-31 for PV DC SPDs.
Do not use AC SPD on the PV DC side DC circuits do not have the same natural current zero-crossing as AC circuits. PV DC SPDs must be selected according to PV voltage, DC application design and the correct DC-side SPD standard.
Type selection

How to choose Type 1, Type 2, Type 1+2 or Type 3 SPD

SPD type should be selected by installation position and surge exposure, not only by the kA number printed on the device.

Tipo SPDPosizione tipicaMain selection meaningKey parameterWhen to consider it
DOCUP di tipo 1Main incoming position or service entranceDesigned for lightning current duty at the entry point of the installation.IimpExternal lightning protection system, overhead line exposure, high lightning risk.
DOCUP di tipo 2Distribution board, sub-panel, control cabinetGeneral secondary surge protection against induced surges and switching transients.In, Imax, UpMost common choice for distribution boards and many OEM electrical assemblies.
SPD Tipo 1+2Main panel or high-exposure system positionCombined device for lightning current capability and secondary surge protection.Iimp, In, Imax, UpMain panels, lightning-exposed sites, industrial systems, solar PV projects.
DOCUP di tipo 3Near sensitive terminal equipmentFine protection close to the protected load, usually after upstream SPD protection.Uoc, UpControl electronics, sensitive loads, equipment with lower withstand voltage.
Selection shortcut Main incoming panel usually points to Type 1 or Type 1+2. Distribution board usually points to Type 2. Sensitive terminal equipment may need Type 3 after upstream protection.
Voltage and poles

Choose the correct voltage rating and pole configuration

Many SPD selection errors happen because the voltage rating or pole configuration is chosen too casually.

AC voltage: check Uc

For AC SPDs, the maximum continuous operating voltage is usually shown as Uc. It must be suitable for the actual AC system voltage and earthing arrangement.

Common AC systems include 230/400V and 277/480V, but final selection depends on local network design.

PV DC voltage: check Ucpv

For solar PV SPDs, check Ucpv against the maximum DC voltage of the PV string, including cold-temperature open-circuit voltage.

1000V DC and 1500V DC PV systems require PV-rated DC SPDs with matching Ucpv.

Poles: match the wiring

Pole selection depends on single-phase, three-phase, neutral arrangement, TT/TN/IT earthing system, and PV DC protection mode.

Common options include 1P, 2P, 3P, 4P, 3P+N and PV DC configurations.
SistemaConfigurazione SPD comuneCosa confermare
CA monofase1P+N or 2P SPDLine, neutral, earthing system, Uc, backup protection.
AC trifase3P, 3P+N or 4P SPDNeutral arrangement, TT/TN system, panel wiring, phase voltage.
PV DCPV DC SPD modulePositive/negative polarity, Ucpv, 1000V/1500V system, Type 2 or Type 1+2.
OEM cabinetSPD pluggable su guida DINModule width, remote signal, indicator window, replacement cartridge, wiring space.
Parameter guide

Key SPD parameters buyers should understand

Do not compare SPDs only by one headline kA number. Use the full parameter set to judge whether the device fits the system.

ParametroSignificatoSelection use
UcMaximum continuous operating voltage for AC SPD.Must be suitable for the normal AC system voltage.
UcpvMaximum continuous operating voltage for PV DC SPD.Must match or exceed the maximum PV DC system voltage according to design.
IimpImpulse current rating commonly used for Type 1 SPD.Important for incoming protection and lightning-exposed systems.
InNominal discharge current, commonly used for Type 2 SPD.Indicates repeated surge discharge capability under defined test conditions.
ImaxMaximum discharge current for Type 2 SPD under defined test conditions.Useful for comparison, but should not be the only selection criterion.
SuLivello di protezione della tensione.Lower Up generally means better voltage limitation, but coordination and installation still matter.
UocOpen-circuit voltage of the combination wave generator, often used for Type 3 SPD testing.Relevant for fine protection near sensitive equipment.
Backup fuse / MCBOvercurrent protection coordinated with the SPD.Must follow the SPD datasheet and available fault current.
Contatto del segnale remotoAuxiliary contact for remote failure indication.Useful for PV combiner boxes, industrial cabinets and monitored systems.
Standard

Which IEC standard should you check?

Standards are part of SPD selection. They help confirm whether the device is designed and tested for the correct application.

StandardCommon applicationPerché è importante
IEC 61643-11Low-voltage AC surge protective devices.Used for AC SPD performance, safety requirements, tests and ratings.
IEC 61643-31SPDs for photovoltaic DC installations up to 1500V DC.Important for PV combiner boxes, inverter DC inputs and solar DC-side protection.
IEC 61643-12Application guidance for AC SPD selection and installation.Useful for coordination, installation position and AC system protection design.
IEC 61643-32Application guidance for PV SPD selection and installation.Useful for PV-side SPD placement, selection and coordination.
UL 1449North American SPD safety standard.Important when the project requires UL-listed or North America-oriented SPD approval.
Procurement advice Before bulk purchase, ask for the datasheet, standard reference, wiring diagram, backup protection recommendation, certification documents where available, and replacement module information.
Installation affects selection

Selection is not complete without installation checks

A suitable SPD can still perform poorly if it is installed in the wrong position or wired incorrectly.

Install near the protected entry point

Main protection should be placed close to the incoming power point or distribution point it protects.

Keep connection leads short

Long and looped wiring increases residual voltage. Keep SPD connection leads short, straight and properly routed.

Ensure proper grounding

SPD performance depends on equipotential bonding and a low-impedance path for surge current.

Coordinate upstream and downstream SPDs

Type 1, Type 2 and Type 3 devices should work as a coordinated protection system, not isolated devices.

Controlla la protezione di backup

The fuse or circuit breaker must match the manufacturer’s recommendation and the available short-circuit current.

Plan maintenance and replacement

Visual indicators, remote signal contacts and replaceable cartridges make inspection easier in industrial and PV systems.

Avoid mistakes

Common SPD selection mistakes

These mistakes are common in sourcing, panel design and project specification.

Choosing only by Imax

Imax is not the whole selection. Voltage, type, Up, installation position, backup protection and standard are also critical.

Using AC SPD for PV DC

A PV DC circuit needs a DC SPD designed for photovoltaic application and suitable Ucpv.

Ignoring Type 1 requirement

Lightning-exposed buildings and systems with external lightning protection may need Type 1 or Type 1+2 protection.

Wrong voltage rating

Uc or Ucpv must fit the actual system voltage, not only the general system name.

Ignoring earthing system

TT, TN and IT systems may require different protection modes and pole arrangements.

No replacement plan

For PV and industrial systems, visual status, remote signal and replacement cartridge design are important for maintenance.

Buyer checklist

What information should you send before asking for SPD selection?

Send these details to get a faster and more accurate recommendation from an SPD supplier.

InformazioniEsempioPerché è importante
Tipo di sistemaAC distribution board, PV DC combiner box, inverter input, control panelDetermines AC or DC SPD direction.
Tensione di sistema230/400V AC, 480V AC, 1000V DC, 1500V DCDetermines Uc or Ucpv selection.
Posizione di installazioneMain panel, sub-panel, combiner box, inverter side, terminal equipmentDetermines Type 1, Type 2, Type 1+2 or Type 3 direction.
Sistema di messa a terraTT, TN-S, TN-C, ITDetermines wiring mode and pole arrangement.
Esposizione ai fulminiExternal LPS, overhead line, exposed PV field, industrial siteHelps judge whether Type 1 or Type 1+2 is required.
Required certificationIEC, CE, TUV, UL, project approvalPrevents mismatch between product and market requirement.
Panel or OEM requirementDIN rail width, remote signal, cartridge, private label, packagingImportant for OEM electrical assemblies and distributor sourcing.
For distributor or OEM bulk orders If you already know the SPD direction but need to confirm the order details, see our complete Lista di Controllo per Ordini Bulk SPD per Distributori e Acquirenti OEM. It covers model confirmation, certificate coverage, OEM label, packaging, sample approval, inspection, and delivery details before mass production.
Perché LEEYEE

LEEYEE support for SPD selection and sourcing

LEEYEE supplies surge protective devices for solar PV, distribution boards, industrial control panels, telecom, low-voltage systems and OEM electrical assemblies.

AC and DC SPD coverage

Support for AC Type 1, Type 2, Type 1+2 and PV DC SPD options for 1000V and 1500V solar systems.

OEM and distributor support

Pluggable modules, DIN rail design, remote signal contacts, private label, packaging and model selection support.

Clear selection communication

We help buyers confirm system voltage, circuit type, SPD type, poles, standard, backup protection and application match before ordering.

FAQ

SPD selection guide FAQ

Short answers for buyers who need to choose the right surge protective device quickly.

Come scelgo il giusto SPD?

Scegliere il giusto SPD prima identificando se il circuito protetto è in AC o in DC. Quindi selezionare il tipo di SPD in base alla posizione di installazione, abbinare Uc o Ucpv alla tensione del sistema, verificare Iimp, In, Imax e Up, confermare i poli e il sistema di messa a terra, e verificare la protezione di backup e lo standard applicabile.

Qual è il primo passo nella selezione SPD?

Il primo passo è confermare se il circuito protetto è in corrente alternata (AC) o in corrente continua (DC). Le SPD AC e le SPD DC non sono intercambiabili. I sistemi fotovoltaici in DC dovrebbero utilizzare SPD DC progettate per applicazioni fotovoltaiche.

Qual è la differenza tra SPD di Tipo 1 e Tipo 2?

Il Tipo 1 SPD è tipicamente utilizzato nella posizione di ingresso principale o all'ingresso del servizio dove potrebbe essere necessario il dovere di corrente di fulmine. Il Tipo 2 SPD è comunemente utilizzato nei quadri di distribuzione e nei sottopannelli per la protezione secondaria dalle sovratensioni.

Quando dovrei scegliere SPD di tipo 1+2?

Scegliere il tipo 1+2 SPD quando l'installazione richiede sia la capacità di corrente di fulmini che la protezione da sovratensioni secondarie in un unico dispositivo, come i pannelli principali, i siti industriali esposti ai fulmini o i sistemi solari fotovoltaici con un rischio maggiore di fulmini.

Posso utilizzare un SPD AC sul lato DC di un sistema solare FV?

No. Il lato DC di un sistema fotovoltaico deve utilizzare un SPD DC progettato per applicazioni fotovoltaiche. La selezione deve basarsi su Ucpv, tensione del sistema fotovoltaico, polarità, requisiti di Tipo 2 o Tipo 1+2 e il corretto standard del lato DC.

Quale SPD dovrei scegliere per un sistema solare da 1500V?

Per un sistema fotovoltaico da 1500V, scegliere uno SPD DC da 1500V certificato per fotovoltaico. Confermare Ucpv, posizione di installazione, requisiti di Tipo 2 o Tipo 1+2, In, Imax, Iimp se necessario e design della disconnessione DC.

È sempre meglio un Imax più alto?

Non sempre. L'Imax è solo un parametro di confronto. Un SPD adeguato deve anche corrispondere al tipo di circuito AC/DC, alla tensione nominale, al tipo di SPD, all'Up, ai poli, al sistema di messa a terra, alla protezione di backup, alla posizione di installazione e ai requisiti normativi.

Gli SPD necessitano di fusibili di backup o interruttori automatici?

Many SPD installations require backup overcurrent protection. The correct fuse or circuit breaker must follow the SPD datasheet, available short-circuit current and installation standard.

What information should I send to an SPD supplier?

Send the system type, AC or DC side, system voltage, installation position, earthing system, lightning exposure, required certification, pole number, monitoring requirement and quantity.

Need help selecting the right SPD?

Send us your system voltage, AC/DC circuit, installation position, earthing system, lightning exposure and required standard. LEEYEE can help match a suitable SPD direction for solar PV, distribution boards, industrial cabinets and OEM assemblies.

For solar PV 1000V / 1500V DC SPD, PV combiner box SPD, inverter-side surge protection.
Per quadri elettrici AC Type 2 SPD, Type 1+2 SPD, 1P/2P/3P/4P DIN rail options.
Per compratori OEM Pluggable modules, remote signal, custom label, packaging and sourcing support.