Technical data
| Rated supply voltage | AC220V | |||||||
| Operation voltage range | AC80V~440V (Single phase) | |||||||
| Ratedfrequency | 50/60Hz | |||||||
| Overvoltage(>V)setting range | 240V~300V | |||||||
| Undervoltage(<V)seltingrange | 140V~210V | |||||||
| Current | 63A/80A/100A | |||||||
| Error | 2% | |||||||
| >Vand < Vtrip delay | 0.5s | |||||||
| Reset/start delay | 1s~300s | |||||||
| Voltagemeasurermentaccuracy | 1%(Not exceeding 1% of the overall range) | |||||||
| Rated insulation voltage | 400V | |||||||
| Output contact | 1NO | |||||||
| Electrical life | 3 | |||||||
| Mechanicallife | 10⁵ | |||||||
| Protection degree | 10⁶ | |||||||
| Pollutiondeqree | IP20 | |||||||
| Altitude | ≤2000m | |||||||
| Humidity | ≤ 50%at40C(without condensnton) | |||||||
| Storage temperature | -30℃ ~70℃ | |||||||
Default setting
| Technical parameter | Setting range | Step | Factory setting | ||||
| Overvoltage trip value | 240V~300V | 1V | 270V | ||||
| Undervoltage trip value | 140V~210V | 1V | 170V | ||||
| Reset delay time | 1s~300s | 1s | 30s | ||||
| Starting delay time | 1s~300s | 1s | 2s | ||||
| Current specification | 40A | 50A | 63A | 80A | 100A | ||
| Rated operating current(In.A) | 40 | 50 | 63 | 80 | 100 | ||
| Maximum operating current Imax (A.within 10min) |
50 | 60 | 80 | 90 | 100 | ||
| Max.power ofload(kW) | 8.8 | 11 | 13.9 | 17.6 | 22 | ||
Function setting

Overvoltage:240V~300V-OFF
Undervoltage:140V~210V-OFF
Overcurrent: 63A,8 0A,100A
Function/delayed:1s~300s
To quickly adjust the figures for longer periods of time, press either
the ‘Up’ or the‘Down’Keys
Functional interface display