Numéro d'article : LY1-C40/3(S)+1

Key Specifications:

Modèle
LY1-C40/3(S)+1

Type
Class II / Type 2 AC SPD

Pôles
3P+N Pluggable Design

Mode de protection
L-N / N-PE

Voltage Options
75V / 150V / 275V / 320V / 385V / 440V AC

In / Imax
20kA / 40kA, 8/20μs

Protection Elements
MOV + GDT

Montage
35mm DIN Rail

Citer maintenant

    Coordinated Type 2 AC Surge Protection for 3P+N Systems

    LY1-C40/3(S)+1 is a pluggable 3P+N Type 2 AC surge protective device designed for three-phase plus neutral distribution systems. Coordinated MOV and GDT protection paths help limit transient overvoltage between L-N and N-PE while providing fast response and reliable protection for multi-pole AC circuits.


    3P+N Type 2 AC SPD for three-phase distribution boards

    20kA nominal and 40kA maximum discharge current

    MOV protection for L-N and GDT protection for N-PE coordination

    Replaceable pluggable modules with optional remote status contact

    Suitable Applications

    LY1-C40/3(S)+1 is suitable for three-phase plus neutral AC systems requiring coordinated Type 2 surge protection at the sub-distribution or equipment-panel level.

    Distribution Boards

    For coordinated L-N and N-PE protection in three-phase plus neutral distribution boards.

    Industrial Control Panels

    Suitable for industrial control cabinets, machinery panels, HVAC systems, and automation equipment.

    🏢

    Bâtiments commerciaux

    Helps protect three-phase building power systems from switching surges and lightning-induced overvoltage.

    Solar AC Panels

    For the AC side of solar installations when voltage rating and 3P+N protection design match the system.

    FAQ

    Common questions about LY1-C40/3(S)+1 pluggable 3P+N Type 2 AC surge protective device selection.

    What is LY1-C40/3(S)+1 used for?

    It is used for Type 2 surge protection in three-phase plus neutral AC distribution systems, with coordinated protection between L-N and N-PE.

    What does 3P+N mean?

    3P+N means the SPD is designed for three-phase plus neutral systems, with L-N protection across the phases and coordinated N-PE protection.

    Why does this model use MOV and GDT protection?

    MOV elements provide fast voltage clamping on the L-N paths, while the GDT supports coordinated discharge on the N-PE path with low leakage during normal operation.

    What discharge current ratings does it provide?

    The SPD provides 20kA nominal discharge current In and 40kA maximum discharge current Imax for both L-N and N-PE protection paths.

    What voltage options are available?

    L-N maximum continuous operating voltage options include 75V, 150V, 275V, 320V, 385V, and 440V AC. The N-PE continuous operating voltage is 255V.

    What should be confirmed before ordering?

    Confirm the system voltage, 3P+N arrangement, L-N and N-PE protection mode, backup fuse, wiring cross-section, DIN-rail space, and remote contact requirement.

    Données techniques

    Electrical, mechanical, and installation data for LY1-C40/3(S)+1 pluggable 3P+N Type 2 AC surge protective device selection.

    Paramètres75V150V275V320V385V440V
    Électrique IEC
    Nominal AC Voltage Uo / Un60V120V230V230V230V400V
    Maximum Continuous Operating Voltage Uc, L-N75V150V275V320V385V440V
    Maximum Continuous Operating Voltage Uc, N-PE255V
    Nominal Discharge Current In, L-N / N-PE20kA / 20kA, 8/20μs
    Maximum Discharge Current Imax, L-N / N-PE40kA / 40kA, 8/20μs
    Voltage Protection Level Up, L-N / N-PE0.4kV / 1.5kV1.0kV / 1.5kV1.5kV / 1.5kV1.6kV / 1.5kV1.8kV / 1.5kV2.0kV / 1.5kV
    Follow Current Interrupt Rating Ifi, N-PE100 ARMES
    Response Time tA, L-N / N-PE<25ns / <100ns
    Back-Up Fuse Max.315A / 250A gG
    Short-Circuit Current Rating ISCCR, L-N25kA / 50kA
    TOV Withstand 5s UT, L-N90V180V335V335V335V580V
    TOV 120min UT, L-N115V230V440V440V440V765V
    TOV ModeRésistanceRésistanceDéfaut de sécuritéDéfaut de sécuritéDéfaut de sécuritéDéfaut de sécurité
    TOV Withstand 200ms UT, N-PE1200V
    Mécanique et environnement
    Plage de température de fonctionnement-40°C to +70°C
    Humidité de fonctionnement admissible5%–95%
    Atmospheric Pressure / Altitude80kPa–106kPa / -500m to 2000m
    Couple de serrage de la vis de fixation39.9lbf·in / 4.5Nm
    Conductor Cross Section Max.2 AWG solid/stranded; 4 AWG flexible; 35mm² solid/stranded; 25mm² flexible
    Montage35mm DIN Rail, EN 60715
    Degré de protectionIP20, built-in
    Matériau du boîtierThermoplastic, UL94 V-0
    Protection thermiqueOui
    État de fonctionnement / Indication de défautGreen: OK / Red: Defect
    Remote ContactsEn option
    Capacité de commutation RCAC 250V / 0.5A; DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
    RC Conductor Cross Section Max.16 AWG solid / 1.5mm² solid
    Selection Note:
    Confirm the required L-N voltage rating, 3P+N system arrangement, N-PE protection, backup fuse, wiring size, DIN-rail space, and optional remote contact before ordering.

    ■ Configuration interne


    ■ Dimensions et emballage


    ■ Schéma de connexion

    Commencez à personnaliser maintenant

    Nous offrons une gamme complète de services personnalisés, en travaillant en étroite collaboration avec nos clients à chaque étape, de la conception à la livraison finale.

    Autres&Produits

    Notre équipe est toujours guidée par les besoins de nos clients, fournissant une consultation et un soutien professionnels pour assurer votre satisfaction.

    TOUT CE QUE VOUS N'AVEZ PAS PU TROUVER?

    Parlez avec nos vendeurs

    Nous savons que chaque entreprise est unique, c'est pourquoi nous proposons des services personnalisés afin de garantir que nos produits répondent parfaitement à vos besoins spécifiques :

    • Brochure complète à télécharger
    • 15 ans d'expérience en usine
    • Livraison rapide
    • OEM&ODM
    • Prix bas
    • Petit MQQ

    ENVOYEZ-NOUS UN COURRIEL

    devin@cnspd.com

    Nous contacter

    Nous évaluons et améliorons constamment nos processus pour nous assurer que nous fournissons les produits électriques les plus efficaces et les plus fiables du marché.