Type 1 vs Type 2 vs Type 3 SPD: What Is the Difference?

SPD Classification Guide

Compare Type 1, Type 2 and Type 3 surge protective devices by installation position, test waveform, current rating and protection role.

Direct answer: Type 1 SPDs discharge high-energy lightning impulse current at the origin of an installation. Type 2 SPDs limit induced lightning and switching surges in distribution boards. Type 3 SPDs provide final protection close to sensitive equipment.

Type 1, Type 2 and Type 3 SPD Quick Comparison

The easiest way to understand the three SPD types is to connect each type with its normal position in the electrical installation.

SPD typeTypical positionMain protection rolePrincipal test dutyCommon key rating
Tipo 1Origin or main incoming boardDischarges high-energy partial lightning current10/350 μs impulse currentIimp
Tipo 2Main or sub-distribution boardLimits induced lightning and switching surges8/20 μs discharge currentIn and Imax
Tipo 3Close to sensitive terminal equipmentLimits remaining residual overvoltageCombination-wave testUoc and Up
Simple protection path: incoming supply → main distribution → sensitive equipment normally corresponds to Type 1 → Type 2 → Type 3.

What Is a Type 1 Surge Protective Device?

A Type 1 SPD is designed for installation where partial lightning current may enter the low-voltage electrical system.

It is commonly considered at the origin of an installation, particularly where the building has an external lightning protection system or where the incoming supply arrangement creates significant lightning-current exposure.

What does a Type 1 SPD do?

A Type 1 SPD diverts high-energy impulse current toward the equipotential bonding and earthing system. Its main role is to prevent lightning current from passing uncontrolled through the internal electrical installation.

Type 1 test waveform

Type 1 SPDs are tested using a 10/350 μs current impulse. The main rating associated with this test is Iimp, or impulse discharge current.

Iimp should not be compared directly with the Imax value of a Type 2 SPD because the two ratings use different waveforms and represent different test duties.

Where is a Type 1 SPD installed?

  • Service entrance;
  • Main low-voltage switchboard;
  • Origin of the electrical installation;
  • Lightning protection zone transition where partial lightning current is expected.

When should Type 1 be considered?

  • The building has an external lightning protection system;
  • The incoming supply is exposed to lightning-current entry;
  • A project risk assessment identifies partial lightning current;
  • National installation rules specify Type 1 protection;
  • The installation is critical infrastructure with a defined lightning protection concept.
Important limitation: Type 1 primarily manages high-energy current. It does not automatically guarantee sufficiently low residual voltage at every distant or sensitive load.

What Is a Type 2 Surge Protective Device?

A Type 2 SPD is the most common distribution-level surge protective device in low-voltage electrical installations.

It limits transient overvoltages caused by indirect lightning effects, switching operations and residual surge energy from an upstream protection stage.

What surge sources does Type 2 address?

  • Indirect lightning effects;
  • Switching operations;
  • Motors and transformers;
  • Utility-network disturbances;
  • Residual surge energy after an upstream SPD.

Type 2 test waveform

Type 2 SPDs are tested using the 8/20 μs current waveform. Important ratings include In, Imax, Su e Uc.

Where is a Type 2 SPD installed?

  • Main distribution boards;
  • Sub-distribution boards;
  • Machine-control cabinets;
  • Industrial panels;
  • Commercial electrical panels;
  • Solar inverter AC distribution panels.

When may Type 2 be sufficient?

A Type 2 SPD may be sufficient at the origin of some installations where the system is not expected to carry partial lightning current.

This may include certain installations with:

  • Underground incoming supply;
  • No external lightning protection system;
  • Lower assessed lightning-current exposure;
  • No upstream Type 1 duty requirement.
This is not a universal rule. Final selection must follow the applicable installation requirements and project risk assessment.

What Is a Type 3 Surge Protective Device?

A Type 3 SPD provides point-of-use protection for sensitive terminal equipment. It limits residual surge voltage remaining after upstream protection or developing along downstream conductors.

Where is Type 3 installed?

Type 3 is installed close to protected equipment, including:

  • PLCs;
  • Servers;
  • Control systems;
  • Communication equipment;
  • Medical equipment;
  • Sensitive power supplies;
  • Electronic household equipment.

Type 3 protection may be built into socket outlets, power strips, equipment-protection modules, control-panel devices or terminal-protection units.

Type 3 test method

Type 3 devices are commonly evaluated with a combination-wave generator producing a 1.2/50 μs open-circuit voltage waveform and an 8/20 μs short-circuit current waveform. Relevant ratings may include Uoc e Su.

Can Type 3 be used alone?

Type 3 should not normally be expected to discharge the high surge energy present at the service entrance or main distribution level.

Type 3 is normally used as terminal protection within a coordinated system, not as a substitute for correctly selected upstream protection.

Technical Comparison: Type 1 vs Type 2 vs Type 3

Comparison itemDOCUP di tipo 1DOCUP di tipo 2DOCUP di tipo 3
Main roleLightning-current dischargeDistribution-level surge limitationFinal equipment protection
Typical positionOrigin or main incoming boardMain or sub-distribution boardClose to terminal equipment
Test classClass IClass IIClass III
Principal waveform10/350 μs8/20 μsCombination wave
Important ratingIimpIn and ImaxUoc
Also evaluateUc, Up and fault behaviourUc, Up and short-circuit ratingUp and load compatibility
Typical surge environmentPartial lightning currentInduced lightning and switching transientsResidual surge voltage
Can it protect the whole installation alone?Not necessarilyNot necessarilyNo
Common technologySpark gap, MOV or combined technologyMOV-based or combined technologyCompact MOV, GDT or filter-based protection

10/350 μs vs 8/20 μs: Why the Test Waveform Matters

A current value shown in kiloamperes is meaningful only when the associated waveform and rating definition are also known.

10/350 μs vs 8/20 μs waveform comparison for SPD selection
The 10/350 μs waveform is associated with Type 1 lightning-current duty, while the 8/20 μs waveform is associated with Type 2 discharge-current testing. The kA value should always be read together with the waveform and SPD classification.
Always compare the waveform, rating definition, current per protection mode, voltage protection level and full SPD classification.

Iimp vs In vs Imax vs Uoc

These values describe different tests and should not be treated as interchangeable versions of the same current rating.

Iimp Impulse discharge current associated with the Type 1 10/350 μs test.
In Nominal discharge current associated with the Type 2 8/20 μs test.
Imax Maximum discharge current associated with a Type 2 8/20 μs test.
Uoc Open-circuit voltage of the combination-wave generator used for Type 3 testing.

Other important values include Uc, Up, short-circuit current rating and backup protection requirements.

How Type 1, Type 2 and Type 3 SPDs Work Together

Effective surge protection is based on coordinated protection stages, not simply on installing the SPD with the largest current rating.

A typical concept may use:

  1. Tipo 1 at the origin to discharge partial lightning current;
  2. Tipo 2 in a downstream distribution board to limit remaining overvoltage;
  3. Tipo 3 near sensitive equipment to reduce final residual surge voltage.

This does not mean every building must use three separate SPDs. Possible alternatives include Type 1+2 combined SPDs, Type 2+3 combined SPDs, or Type 2 protection at the origin where Type 1 duty is not required.

Is a 10-meter distance always required?
No single cable-distance rule should be applied to every SPD combination. Required coordination depends on SPD technology, manufacturer-tested coordination, conductor arrangement, protection levels and the protected equipment.

What Is a Type 1+2 Combined SPD?

A Type 1+2 SPD is tested for both Type 1/Class I and Type 2/Class II duties. It combines lightning impulse-current discharge and distribution-level surge-voltage limitation.

A Type 1+2 SPD may be useful where:

  • Both protection duties are required at one installation point;
  • Main-board space is limited;
  • Separate SPD coordination would be difficult;
  • A compact internally coordinated solution is preferred.
Type 1+2 does not automatically mean no downstream protection is required. Remote panels and sensitive equipment may still need additional coordinated Type 2 or Type 3 protection.

For complete Type 1+2 selection guidance, see the dedicated Type 1+2 SPD guide.

Which SPD Type Do You Need?

The following table provides an initial direction. Final selection must still follow the actual system design and applicable requirements.

Project situationInitial selection direction
Building has an external lightning protection systemConsider Type 1 or Type 1+2
Partial lightning current may enter the installationType 1 duty is required
General main-panel protection without Type 1 dutyTipo 2
Sub-distribution or machine-control panelTipo 2
Sensitive terminal equipmentType 3 near the equipment
Type 1 and Type 2 duties are required in one main boardType 1+2
Equipment is far from the main SPDConsider additional Type 2 or Type 3
Surge protection is required on a solar PV DC circuitUse a PV-specific DC SPD

How to Select the Correct SPD Type

  1. Identify the installation position. Is the SPD installed at the origin, distribution board, machine panel or terminal equipment?
  2. Assess lightning exposure. Check the external lightning protection system, incoming supply and lightning protection zones.
  3. Confirm AC or DC application. Do not use a normal AC SPD on the DC side of a photovoltaic system.
  4. Confirm the earthing system. Identify TN-S, TN-C, TT, IT or the relevant DC grounding arrangement.
  5. Check the full rating set. Review Uc, Up, Iimp, In, Imax, Uoc, short-circuit rating and backup protection.
  6. Verify coordination. Check the relationship between upstream protection, downstream SPDs and protected equipment.

Common SPD Selection Mistakes

  • Choosing only by the largest kA value. A larger current number does not correct the wrong waveform, voltage rating or circuit configuration.
  • Comparing Iimp directly with Imax. These values represent different test duties and different waveforms.
  • Using Type 3 as the main building SPD. Type 3 is intended for final equipment protection, not high-energy incoming surge current.
  • Assuming Type 1 protects every load. Residual voltage and downstream conductor effects may still require additional protection.
  • Using a fixed 10-meter rule. Coordination must follow the selected SPD technologies and manufacturer documentation.
  • Ignoring Uc and Up. Current capacity alone does not determine voltage compatibility or equipment protection.
  • Using an AC SPD on PV DC. Photovoltaic DC circuits require application-specific voltage and disconnection characteristics.
  • Ignoring short-circuit coordination. The SPD, backup fuse and prospective short-circuit current must be compatible.

IEC and UL SPD Types Are Not Identical Definitions

IEC and UL systems both use Type 1, Type 2 and Type 3 terminology, but the classifications should not be treated as fully interchangeable.

Under the IEC framework, the types are closely associated with test classes, waveforms and protection duties. Under UL 1449, SPD types are strongly related to the permitted connection location and installation relative to service equipment and overcurrent protection.

For North American projects, confirm:

  • UL listing;
  • SPD type;
  • Nominal discharge current;
  • Voltage protection rating;
  • Short-circuit current rating;
  • Permitted connection location.
Do not convert IEC and UL classifications solely by matching the type number.

Type 1 vs Type 2 vs Type 3 SPD FAQ

What is the main difference between Type 1, Type 2 and Type 3 SPD?

Type 1 manages lightning-current duty at the origin, Type 2 provides distribution-level surge protection, and Type 3 limits residual surge voltage close to sensitive equipment.

Is Type 1 better than Type 2?

No. They perform different roles. Type 1 handles lightning-current duty, while Type 2 limits transient overvoltage in the electrical distribution system.

Can Type 2 be installed at the main distribution board?

Yes. Type 2 is commonly installed in main and sub-distribution boards where Type 1 lightning-current duty is not required or where an upstream Type 1 stage already exists.

Does every installation need a Type 1 SPD?

No. The need for Type 1 depends on lightning-current exposure, external lightning protection, the incoming supply arrangement and applicable project requirements.

Can Type 3 SPD be used without Type 1 or Type 2?

Type 3 should not normally be relied upon as the only protection where high-energy surges may enter the installation. It is intended primarily as coordinated terminal protection.

Is Type 1+2 the same as Type 1 and Type 2?

A Type 1+2 SPD is tested for both Type 1 and Type 2 duties within one product. Separate Type 1 and Type 2 devices can provide the same stages, but their coordination must be verified.

Qual è la differenza tra Iimp e Imax?

Iimp is associated with the 10/350 μs Type 1 impulse-current test. Imax is associated with the 8/20 μs Type 2 maximum discharge-current test.

Can LEEYEE help select the correct SPD type?

Yes. Provide the system voltage, AC or DC application, earthing arrangement, installation position, poles, required ratings and project quantity.

Related Surge Protection Guides

Need Help Selecting the Correct SPD Type?

Send the AC or DC application, system voltage, earthing arrangement, installation position, required poles, current ratings and project quantity. LEEYEE will help identify a suitable surge protection configuration.

Articolo precedente.
Perché è necessario un dispositivo di protezione contro le sovratensioni di tipo 2 per gli impianti elettrici
Articolo successivo.
Connettori e cavi per pannelli solari
Devin Ling - Electrical Engineer at LEEYEE Electrics

Devin Ling

Ingegnere elettrico presso LEEYEE Electrics

Oltre 10 anni nei dispositivi di protezione dalle sovratensioni
Specializzato in IEC 61643 / UL 1449
Esperienza in impianti solari fotovoltaici e industriali

Parlare con un ingegnere Ottenere una raccomandazione tecnica

Non siete sicuri di quale SPD sia adatto al vostro sistema?
Ottenete una rapida raccomandazione dai nostri ingegneri.

Informazioni su LEEYEE:

Fondata nel 2009, LEEYEE è un produttore specializzato in dispositivi di protezione a bassa tensione. Possediamo i certificati CE, CB, ISO9001 e TUV. Inoltre, supportiamo le opzioni di personalizzazione per l'aspetto del colore, i parametri e i loghi. Per consultare i cataloghi dei prodotti e le richieste di informazioni, è possibile contattarci via e-mail all'indirizzo max@cnspd.com.

Cita ora

    Elettrico LEEYEE

    Correlato
    Prodotti