Automatic Transfer Switch for Industrial Plants and Factory Control Panels

An automatic transfer switch can be useful in a factory without being responsible for the entire factory power system. For a compact ATS, the more realistic industrial application is usually a selected low-voltage load group: a control panel, a small distribution board, a generator-backed auxiliary circuit or another group of loads that can tolerate a short interruption during transfer.

Quick Answer: Where Does a Compact ATS Fit in a Factory?

A compact open-transition ATS is best evaluated around the specific loads connected to the transfer circuit, not the total connected load of the plant. Confirm the simultaneous load current, important motor starting conditions, generator capability, system voltage, required poles and upstream protection before selecting the ATS. IEC 60947-6-1 provides the IEC product-standard framework for transfer switching equipment.[1]

Select Backup Loads → Verifique la corriente de carga → Check Motors → Confirm Generator → Select 2P / 3P / 4P
Product scope LEEYEE's standard ATS is a compact integrated open-transition product for low-voltage dual-source switching. This guide therefore focuses on selected factory loads, control panels and sub-distribution circuits. It does not present the compact product as a large draw-out ATS, bypass-isolation system, closed-transition system or complete plant-wide main switchboard.
LEEYEE compact automatic transfer switches in 2-pole and 4-pole configurations
LEEYEE compact integrated ATS products shown in 2-pole and 4-pole configurations. The final model must be matched to the project voltage, current, neutral arrangement, source configuration and required control functions.

Which Factory Loads Are More Suitable for a Compact ATS?

The key question is not “How large is the factory?” It is “Which loads will actually pass through this ATS?”

A compact ATS is more naturally applied to a defined low-voltage load group rather than to the full incoming supply of a large industrial facility.

The examples below are practical application categories, not automatic approvals. Actual suitability must still be checked against the selected ATS data and project conditions.

Load or Circuit Typical Fit Qué Confirmar
PLC and control circuits Often suitable Allowed interruption and control-power requirements
Small control panels Often suitable Total current and control logic
Small distribution boards Often suitable Maximum simultaneous load and protection
Lighting and monitoring circuits Often suitable Load current and required backup duration
Small pumps and fans Needs checking Motor starting current and switching duty
Large compressors or heavy motors Requires detailed engineering review Starting method, utilisation duty, generator response and ATS capability
Plant-wide main incoming supply Not automatically within compact ATS scope Complete switchboard architecture and project requirements

Procurement conclusion: select the ATS around the actual transferred load group. Do not use total transformer capacity or total factory connected load as the only sizing basis.

Significado para el comprador When requesting a quotation, tell the supplier which circuits must remain available during a utility outage. A clear emergency-load list is more useful than simply saying “factory load” or sending only the transformer rating.

Typical Utility-to-Generator Arrangement

A common industrial backup arrangement uses the utility as the normal source and a generator as the standby source. Both sources are connected to the transfer system, while the ATS supplies the selected backup-load circuit.

Industrial plant automatic transfer switch diagram showing utility, generator, protective devices, ATS and selected critical loads
Typical utility-to-generator arrangement for selected industrial loads. The ATS transfers the defined backup circuit between sources; upstream protection and the exact distribution architecture must be confirmed for the project.

When the normal source becomes unacceptable and the generator reaches the required operating condition, the ATS can transfer the connected load to the emergency source. After normal power is restored and the programmed conditions are satisfied, the load can transfer back.[2]

Open-transition means a short interruption LEEYEE's standard compact ATS is intended for open-transition switching. This is a break-before-make process: the first source is disconnected before the second source is connected. The load therefore experiences an interruption during transfer.[2] If the process cannot tolerate that interruption, the overall power-continuity design needs a different engineering solution.

Do Not Treat a Compact ATS as the Entire Factory Power System

An ATS performs one main job: it transfers a load between available power sources. It does not automatically replace the other protection, distribution and continuity functions required in an industrial electrical system.

Upstream circuit-breakers, conductors, generator controls and the transfer switch must therefore be considered together. IEC 60947-2 covers low-voltage circuit-breakers, while IEC 60947-6-1 covers transfer switching equipment.[1][3]

Significado de ingeniería Do not assume that installing an ATS eliminates the need for an MCCB or another required protective device. The available fault current, breaker characteristics, conductor design and ATS short-circuit data must be reviewed for the actual installation.

How Should the ATS Current Rating Be Selected?

Start with the maximum current expected to pass through the ATS during normal transferred operation. Then check whether the load characteristics create additional requirements.

For a compact industrial ATS application, confirm:

  • Voltaje y frecuencia del sistema of both sources.
  • Maximum simultaneous load current of the transferred circuit.
  • Tipo de carga, especially motors and inductive loads.
  • ATS utilisation data for the intended switching duty.
  • Número de polos and whether the neutral must be switched.
  • Corriente de falla disponible at the installation point.
  • Dispositivo de protección aguas arriba and required coordination.
  • Installation conditions, including enclosure and ambient conditions where relevant.
Avoid simple oversizing formulas Do not assume that every industrial ATS can be selected by multiplying the running current by a fixed factor such as 1.5 or 2. Motor starting, switching duty, generator performance, protective-device coordination and installation conditions may all change the final selection.

Why Do Motor Loads Need Extra Attention?

Motors can draw much more current during starting than during normal running. This means that a small pump, fan or machine auxiliary motor cannot be evaluated only from its steady-state current.

Generator application guidance also shows that motor starting can produce substantial transient demand and voltage dip. Generator response depends on factors such as starting kVA, starting method, alternator characteristics and engine response.[4][5]

  1. Identify the motors on the backup circuit. Do not mix the complete factory motor list with the motors actually supplied through this ATS.
  2. Record the motor rating and starting method. Direct-on-line, soft-start and variable-frequency-drive applications can create different system behaviour.
  3. Check whether several motors can start together. Simultaneous starting can create a larger transient demand.
  4. Confirm generator capability. Check acceptable voltage and frequency performance during the expected starting event.
  5. Confirm the ATS switching duty. The ATS must be suitable for the actual load type and application.
Significado para el comprador For a small pump or fan circuit, send the motor power, rated current and starting method together with the ATS enquiry. For a large compressor, heavy conveyor or major production motor, do not assume suitability merely because its running current is below the ATS nominal current.

Should a Factory ATS Be 3P or 4P?

Pole selection depends on the electrical system and neutral arrangement, not simply on whether the system is three-phase.

A 3P ATS switches the three phase conductors while leaving the neutral unswitched. A 4P ATS switches the neutral together with the phase conductors. Whether the neutral should be switched depends on the generator connection, earthing and bonding arrangement, protection design and applicable project requirements.[2]

Information required for pole selection Send the system voltage, single-line diagram, generator neutral arrangement, earthing system and intended neutral connection. If those details are not known, do not choose 3P or 4P from voltage alone.

How Should the ATS Work With MCCBs?

Dispositivo Main Job What the Buyer Must Check
ATS / ATSE Transfers the selected load between sources Current, poles, transfer logic and switching data
MCCB / circuit-breaker Provides the specified circuit switching and protection functions Breaking capacity, trip settings and coordination
Generator controller Starts and monitors the generator set Start request, voltage/frequency readiness and operating sequence

Procurement conclusion: matching the ampere number printed on an ATS and an MCCB does not prove that the combination is correctly coordinated.

What Happens During a Utility Failure?

The exact thresholds and delay settings depend on the controller and project, but a typical utility-to-generator sequence follows this logic:

  1. The normal source becomes unacceptable. The controller monitors the source according to its available sensing functions.
  2. The generator receives a start request. The generator starts and reaches acceptable operating conditions.
  3. The ATS transfers the selected load. In open transition, the normal source is disconnected before the emergency source is connected.
  4. The generator supplies the backup circuit. The generator must support the actual running and transient load.
  5. The load retransfers when normal power returns. Retransfer and generator cooldown timing depend on the controller and generator-system settings.

Which ATS Indications Are Useful in a Factory Panel?

Maintenance personnel should be able to understand source availability and load position without guessing the current switch state.

For LEEYEE compact ATS project confirmation, useful functions can include:

  • Normal Available
  • Emergency Available
  • Load to Normal
  • Load to Emergency
  • Auto / Manual
  • Fault Alarm, where provided by the selected configuration

If remote indication, generator-start contacts, dry-contact status, BMS integration or communication is required, specify the exact signal list before ordering. Do not assume that every controller version provides the same terminals or communication functions.

When Is This Compact ATS a Good Match?

Aplicación Suitability Significado de Ingeniería
Utility + standby generator Aplicación típica Confirm current, voltage, poles and control logic
Factory control panel Potentially suitable Confirm transferred load and allowable interruption
Small backup distribution board Potentially suitable Check maximum simultaneous load and protection
Small pump or fan backup circuit Needs motor check Confirm motor starting and ATS switching duty
Large factory main incoming system Not automatically suitable Requires complete switchboard and protection review
No-break process Not suitable by itself Open transition causes an interruption
Bypass-isolation requirement Not the standard compact product Requires a separate engineered architecture

The product should be selected where a compact open-transition ATS matches the actual electrical and process requirement, rather than forcing the product into a higher-level industrial application for which it was not intended.

¿Qué información deberías enviar antes de hacer un pedido?

A useful industrial ATS enquiry should describe the transferred circuit, not just provide one ampere value.

Normal source: voltage and frequency
Emergency source: generator voltage and frequency
Phase system: single-phase or three-phase
Pole requirement: 2P, 3P or 4P
Transferred load: maximum simultaneous current
Motor loads: rating and starting method
Neutral arrangement: earthing and bonding details
Protección: upstream MCCB or breaker information
Fault level: available short-circuit information where required
Control functions: start signal, status and alarm requirements
Panel requirement: installation space and arrangement
Project document: single-line diagram where available

Need help confirming a compact ATS for a factory panel?

Send the system voltage, backup-load current, motor information, pole requirement, generator details and single-line diagram. LEEYEE can help confirm whether the compact open-transition ATS configuration matches the intended application.

PREGUNTAS FRECUENTES

Can this ATS supply an entire factory?
Do not assume so. A compact ATS is better evaluated around the specific load group connected to it. Large plant-wide incoming systems may require a different switchgear architecture, higher ratings and additional engineering functions.
Can a compact ATS be used for factory control panels?
Yes, when the voltage, load current, pole configuration, switching duty, protection and allowable transfer interruption match the ATS application data.
Can it be used with a standby generator?
Utility-to-generator transfer is a typical application for this type of compact ATS. The generator voltage, frequency, start logic, capacity and neutral arrangement still need to be confirmed.
Can I select the ATS only from the motor running current?
No. Motor starting conditions can place substantially greater transient demand on the generator and switching system than the normal running current indicates.
Does every three-phase factory need a 4P ATS?
No. Whether the neutral needs to be switched depends on the source configuration, generator neutral, earthing and bonding arrangement, protection design and applicable project requirements.
Does the ATS replace an MCCB?
Do not assume that it does. The ATS performs source transfer, while circuit-breakers provide the protection and switching functions required by the distribution design. They should be selected and coordinated together.
Is this ATS suitable for uninterrupted industrial processes?
Not by itself. The standard compact product uses open-transition switching, which introduces an interruption between sources. Processes requiring uninterrupted power need a different continuity architecture.

Referencias

  1. IEC, IEC 60947-6-1:2026 — Aparamenta de baja tensión — Parte 6-1: Equipos multifuncionales — Equipos de conmutación de transferencia. Tienda virtual de la IEC.
  2. Eaton, published technical literature covering automatic transfer switches, open-transition operation and switched-neutral applications. Eaton.
  3. IEC, IEC 60947-2 — Low-voltage switchgear and controlgear — Part 2: Circuit-breakers. Tienda virtual de la IEC.
  4. Cummins Power Generation, generator-set application guidance covering motor starting and transient load behaviour. Cummins Power Generation.
  5. Cummins Power Generation, generator sizing and motor-starting technical guidance. Final generator selection should be confirmed using the applicable generator data and project conditions. Cummins Power Generation.
Publicación anterior.
Hospital Automatic Transfer Switch Guide for Backup Power
Publicación siguiente.
Automatic Transfer Switch for Commercial Buildings: 6A–63A Backup Power Selection Guide
Devin Ling - Ingeniero Eléctrico en LEEYEE Electrics

Devin Ling

Ingeniero eléctrico en LEEYEE Electrics

Más de 10 años en dispositivos de protección contra sobretensiones
Especializado en IEC 61643 / UL 1449
Experiencia en energía solar fotovoltaica y sistemas industriales

Hable con un ingeniero Obtener recomendación técnica

¿No está seguro de qué SPD se adapta a su sistema?
Obtenga una rápida recomendación de nuestros ingenieros.

Acerca de LEEYEE:

Fundada en 2009, LEEYEE es un fabricante especializado en dispositivos de protección de baja tensión. Contamos con los certificados CE, CB, ISO9001 y TUV. Además, admitimos opciones de personalización para el aspecto del color, los parámetros y los logotipos. Si desea consultar catálogos de productos o realizar consultas, puede ponerse en contacto con nosotros a través de la siguiente dirección de correo electrónico max@cnspd.com.

Cotizar ahora

    LEEYEE Eléctrico

    Relacionado
    Productos