Automatic Transfer Switch Surge Protection: Where Should SPDs Be Installed?

An automatic transfer switch and a surge protective device solve two different problems. The ATS transfers a load between available power sources; an SPD limits transient overvoltage and diverts surge current. For a backup-power system, surge protection should therefore be evaluated around the ATS rather than treated as an internal ATS function. [1][2]

Respuesta Rápida

An ATS does not replace an SPD. Surge protection may be considered on the utility input, generator input, ATS output or downstream distribution, but the correct locations depend on the complete power architecture rather than the ATS ampere rating alone. [2][3][4]

For panel builders, the practical question is not “Does every ATS need three SPDs?” It is “Which surge paths exist in this project, what protection already exists, and where should the next coordinated protection stage be placed?”
Utility side Check whether an upstream coordinated SPD already protects the incoming supply.
Generator side Review separately, especially when the generator is outdoors, remote or connected by exposed conductors.
ATS output A downstream SPD may form an additional protection stage for distribution equipment and sensitive loads.
Tipo de SPD Do not choose Type 1 or Type 2 from ATS current alone. Installation position and the complete surge-protection concept matter.
ATS surge protection system diagram showing SPD positions on utility, generator and load sides
Possible SPD positions around a compact automatic transfer switch. The marked positions are engineering options, not a requirement to install an SPD at every point.

ATS and SPD Perform Different Electrical Functions

IEC 60947-6-1:2026 covers transfer switching equipment used to transfer a load between power supply sources. That source-transfer function is fundamentally different from surge protection. [1]

IEC 61643-11:2025 applies to surge protective devices connected to low-voltage AC power systems. These devices are intended to limit surge voltages and divert surge currents arising from lightning effects or other transient overvoltages. [2]

Therefore, an ATS can perform its source-transfer function correctly while the surrounding installation still requires separate surge-protection measures.

LEEYEE compact 2P and 4P automatic transfer switches for normal and emergency power source transfer
LEEYEE compact 2P and 4P automatic transfer switches. These devices perform source transfer between normal and emergency power supplies; surge protection is provided separately by the surrounding electrical system.
LEEYEE product scope

LEEYEE's standard ATS offering is a compact integrated automatic transfer switch, including configurations such as 2P and 4P for normal/emergency source transfer. It is supplied as the ATS device rather than as a complete ATS cabinet, AMF cabinet or bypass-isolation system.

ATS

Transfers the load between normal and emergency power sources.

SPD

Limits transient overvoltage and diverts surge current.

MCCB

Provides circuit interruption, overcurrent protection and isolation according to the selected device and system design.

Significado de ingeniería

A higher-current ATS does not replace an SPD. An SPD does not replace an MCCB. Panel builders should verify source transfer, overcurrent protection, short-circuit performance and surge protection separately, then coordinate them at system level.

Where Can an SPD Be Installed Around an Automatic Transfer Switch?

For engineering review, divide the power path into three areas: the utility or normal source, the generator or emergency source, and the load side after the transfer switch.

Schneider Electric application guidance for automatic transfer switches discusses surge protection at the service-entry side, generator side and transfer-switch load side. System arrangement and existing protection affect the final solution. [5]

This does not mean every ATS installation requires three identical SPDs.

Posición del SPD Why evaluate it? ¿Qué debe confirmarse? Procurement meaning
Utility / normal source Incoming lightning-related or switching transients Service entrance, upstream SPD, earthing and lightning protection concept Check existing upstream protection first
Generator / emergency source Separate surge exposure through generator conductors Generator location, cable route, exposure and existing protection Outdoor and remote circuits deserve separate review
ATS output / load side Additional protection for downstream equipment Load sensitivity, downstream panels and upstream SPD coordination Use as part of a coordinated protection concept

The ATS nameplate alone cannot determine where the SPD belongs. Review the complete single-line architecture first.

Does the Utility Input Side Need Surge Protection?

The utility side is one of the first locations engineers review because transient overvoltages can enter from the incoming power system.

IEC 62305-4:2024 addresses surge-protection measures for electrical and electronic systems within structures exposed to lightning electromagnetic effects. IEC 60364-5-53 covers selection and erection requirements relevant to protective, switching and control equipment in low-voltage installations. [3][4]

If a suitable upstream SPD already exists, another SPD immediately beside the ATS may or may not provide meaningful additional protection.

Scenario: an upstream SPD already exists Confirm its location, type, voltage ratings, protection level and coordination before adding another stage near the ATS.

Does the Generator Input Need Its Own SPD?

The emergency source should be assessed independently because its physical installation may create a different surge path.

An outdoor or remotely installed generator may be connected through long or exposed conductors. That differs from a compact indoor installation with short protected cable runs.

ATS surge-protection application guidance also identifies generator-side power and external control or monitoring circuits as areas that may require separate consideration. [5]

Do not assume every generator input needs the same SPD

Confirm generator location, cable exposure, system voltage, earthing arrangement, existing protection and the applicable project standard before fixing the SPD configuration.

Should the SPD Be Installed Before or After the ATS?

There is no universal “before” or “after” answer.

An upstream SPD can address transient overvoltages arriving from a source. A downstream SPD can form another protection stage closer to distribution equipment or sensitive loads.

Some installations use coordinated SPDs at several levels. A compact installation with suitable upstream protection may not require another device at every possible position.

Decision flow for choosing SPD installation positions around an automatic transfer switch
Decision flow for reviewing utility-side, generator-side and downstream surge protection without assuming every ATS needs the same three-SPD arrangement.

Do You Need SPDs on All Three Sides?

No universal rule requires the same three-SPD arrangement for every ATS system.

Existing service-entrance SPD near the ATS The normal-source side may already have a protection stage. Verify coordination before adding another SPD.
Outdoor generator with a long feeder Generator-side protection deserves stronger consideration because the conductors may form a separate exposure path.
ATS supplies PLC, BMS, UPS or control equipment A downstream SPD may provide an additional coordinated protection stage for sensitive electronics.
Compact indoor system with coordinated upstream protection Do not add another SPD merely because a diagram shows an available installation point.

Type 1 or Type 2 SPD for an ATS System?

Do not determine SPD type from the ATS current rating.

IEC 61643-11:2025 specifies requirements and test methods for SPDs connected to low-voltage AC systems, including requirements relevant to Type 1 and Type 2 devices. [2]

In an IEC-oriented project, Type 1 protection is generally associated with locations where lightning-current discharge capability forms part of the lightning protection concept. Type 2 SPDs are commonly used at distribution levels for transient overvoltage protection and coordinated downstream protection.

Final selection still depends on installation position, external lightning protection, earthing system, existing upstream protection, Uc, Up and required surge-current capability.

Type 1 and Type 2 SPD selection overview for ATS utility generator and load-side applications
Type 1 versus Type 2 is an installation and surge-exposure decision. It should not be inferred from ATS amperage alone.
IEC and UL terminology are not automatically equivalent

IEC and UL use different classification and installation frameworks. Buyers should confirm the required market standard and product certification before OEM approval. [6]

How MCCB, SPD and ATS Work Together

A backup-power panel may use MCCBs or other protective devices together with SPDs and a compact ATS, but each component has a different purpose.

The ATS handles source transfer. The SPD handles transient overvoltage. The MCCB handles circuit protection and switching functions appropriate to its design.

SPD backup protection also requires project confirmation. Fuse or breaker ratings, conductor size, prospective short-circuit current and permitted installation arrangement must follow the selected SPD documentation and applicable standard.

Se requiere confirmación del proyecto

Do not determine conductor size, SPD backup fuse or breaker rating, protection mode, neutral arrangement or short-circuit coordination from a generic article. Confirm the actual SPD model and project conditions.

What Should Buyers Confirm When Ordering ATS + SPD Together?

Prepare the following information:
ATS information
  • Rated system voltage
  • Monofásico o trifásico
  • Corriente nominal
  • 2P, 3P or 4P configuration
  • Normal and emergency source type
  • Open-transition requirement
  • Required standard or project specification
SPD information
  • Voltaje del sistema
  • Disposición de conexión a tierra
  • Proposed installation position
  • Type 1, Type 2 or coordinated protection requirement
  • Uc and Up requirements
  • In, Imax o Iimp cuando sea aplicable
  • Required certification or market standard

LEEYEE supplies compact automatic transfer switches and surge protective devices. The surrounding MCCB arrangement, enclosure, generator controls and complete panel architecture remain project-specific unless separately confirmed.

Need to review an ATS + SPD configuration?

Send the system voltage, ATS current and poles, utility/generator arrangement, earthing system, proposed SPD positions and required standard.

Common ATS Surge-Protection Design Mistakes

1. Treating surge protection as an ATS built-in function

Do not assume a transfer switch includes surge protection unless the actual assembly documentation says so.

2. Installing the same SPD at every possible position

Utility, generator and downstream positions can have different surge exposure, earthing and coordination requirements.

3. Choosing an SPD from ATS current alone

ATS current does not by itself determine SPD Type, Uc, Up, In, Imax or Iimp.

4. Ignoring existing upstream protection

Additional SPDs should be coordinated with devices already installed.

5. Forgetting control and communication circuits

Remote start contacts, BMS links and communication circuits may require separate signal-line protection. Power-line SPDs do not automatically protect every signal interface. [5]

ATS + SPD Combination Sourcing for Panel Builders

ATS and SPD combination sourcing can simplify model confirmation when the system architecture is already known. The benefit is not that they become one device; it is that their requirements can be reviewed together before panel production.

For distribution-level SPD information, see the LEEYEE Type 2 Surge Protective Device. For ATS operating logic and selection, see the LEEYEE Automatic Transfer Switch Selection Guide.

Preguntas frecuentes

Does every automatic transfer switch need surge protection?

Not as a universal rule. Review source exposure, existing protection, generator location, earthing and downstream load sensitivity.

Should an SPD be installed before or after an ATS?

Either or both locations may be appropriate. The final arrangement depends on source exposure and coordination with other SPDs.

Does a generator input need its own SPD?

It depends. Generator-side protection deserves stronger consideration when the generator is outdoors, remote or connected by long or exposed conductors.

Can the same Type 2 SPD be used on utility and generator inputs?

Do not assume so. Each source should be checked for voltage, earthing, installation position and required surge-current capability.

Is an MCCB enough to protect an ATS from surge voltage?

No. MCCBs and SPDs address different electrical events. An SPD is specifically intended to limit transient overvoltage and divert surge current.

Does LEEYEE supply the complete ATS panel?

This article does not make that claim. LEEYEE's standard offering is the compact integrated ATS device, and LEEYEE also supplies surge protective devices. Complete cabinet design and project wiring must be confirmed separately.

Confirm the system before fixing the models

Share the utility and generator voltage, ATS current and poles, earthing system, existing upstream SPD, downstream load type and required project standard.

Referencias

  1. Comisión Electrotécnica Internacional (IEC), IEC 60947-6-1:2026 — Aparamenta de baja tensión — Parte 6-1: Equipos multifuncionales — Equipos de conmutación de transferencia. Página de publicaciones oficiales de la IEC.
  2. Comisión Electrotécnica Internacional (IEC), IEC 61643-11:2025 — Dispositivos de protección contra sobretensiones de baja tensión — Parte 11: Dispositivos de protección contra sobretensiones conectados a sistemas de alimentación de baja tensión de CA — Requisitos y métodos de ensayo. Página de publicaciones oficiales de la IEC.
  3. Comisión Electrotécnica Internacional (IEC), IEC 60364-5-53:2019 + AMD1:2020 + AMD2:2024 — Low-voltage electrical installations — Part 5-53. Página de publicaciones oficiales de la IEC.
  4. Comisión Electrotécnica Internacional (IEC), IEC 62305-4:2024 — Protección contra el rayo — Parte 4: Sistemas eléctricos y electrónicos en estructuras. Página de publicaciones oficiales de la IEC.
  5. Schneider Electric, Locations for a surge protective device in an Automatic transfer switch application, FAQ000255143. Schneider Electric application guidance.
  6. UL Solutions, UL iQ for Surge Protective Devices. UL Solutions certification information.
Publicación anterior.
ATS and UPS Coordination Guide for Critical Loads
Publicación siguiente.
ATS vs AVR for Generator Backup Systems: What’s the Difference?
Devin Ling - Ingeniero Eléctrico en LEEYEE Electrics

Devin Ling

Ingeniero eléctrico en LEEYEE Electrics

Más de 10 años en dispositivos de protección contra sobretensiones
Especializado en IEC 61643 / UL 1449
Experiencia en energía solar fotovoltaica y sistemas industriales

Hable con un ingeniero Obtener recomendación técnica

¿No está seguro de qué SPD se adapta a su sistema?
Obtenga una rápida recomendación de nuestros ingenieros.

Acerca de LEEYEE:

Fundada en 2009, LEEYEE es un fabricante especializado en dispositivos de protección de baja tensión. Contamos con los certificados CE, CB, ISO9001 y TUV. Además, admitimos opciones de personalización para el aspecto del color, los parámetros y los logotipos. Si desea consultar catálogos de productos o realizar consultas, puede ponerse en contacto con nosotros a través de la siguiente dirección de correo electrónico max@cnspd.com.

Cotizar ahora

    LEEYEE Eléctrico

    Relacionado
    Productos